E50C1 Installation Guide
Quick Setup
Instructions
Use this section to enter:
• Modbus communication parameters
• CT (Current Transducer) output voltage and input current ranges
• The service type to be monitored
These instructions assume the meter is set to factory defaults. If it has been previously configured, all optional values should be
checked. For more options (i.e., Potential Transformer ratios, etc.) and the full setup instructions, see the following pages.
A. To Navigate to the Setup screens:
1. Press
+
+
or
–
repeatedly until
SETUP
screen appears.
2. Press to get to the
PASWD
screen.
3. Press to move through the digits. Use the
+
+
or
–
buttons to enter your password (the default is
00000
).
4. Press to move to the first Setup screen (
S COM
)
5. Use
+
+
or
–
to select the parameter screen you want to set.
6. After you set the parameters you want, use
+
+
or
–
to select the next Setup screen or to exit the Setup screens (return to
SETUP
).
B. To Enter Modbus communication parameters:
1. Navigate to the
S COM
(set communications) Setup screen (see section A above).
2. Press to go to the
ADDR
screen and through the address digits. Use
+
+
or
–
to select the Modbus address (default is
001
).
3. Press to accept the value and go to the
BAUD
screen. Use
+
+
or
–
to select the baud rate (default is
19200
).
4. Press to go to the
PAR
screen. Use
+
+
or
–
to select the parity (default is
NONE
).
5. Press to go back to the
S COM
screen.
C. To Enter the CT (Current Transducer) output voltage and input current ranges:
1. Navigate to the
S CT
(Set Current Transducer) Setup screen (see section A above).
2. Press to go to the
CT V
screen. Use
+
+
or
–
to select the voltage mode Current Transducer output voltage (default is
1.00V
).
3. Press to go to the
CT SZ
screen and through the digits. Use
+
+
or
–
to select the CT size in amps (default is
100
). accept the
value and
4. Press to accept the value and go back to the
S CT
screen.
D. To Enter the service type to be monitored:
1. Navigate to the
S SYS
(Set System) Setup screen (see section A above).
2. Press to go to the
SYSTM
screen. Use
+
+
or
–
to select the configuration (see wiring diagrams - default is
40
).
Press to go back to the
S SYS
screen. For full setup instructions, see the configuration instructions on the following pages.