Z207061-0A
Page 2 of 2
©2015 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 0415
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
AG01E Installation Guide
TM
Installation
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Disconnect and lock out all power sources before beginning the installation of the sensor.
2. Install the GWN Series gas platform according to the instructions included with that device.
3. Remove the front cover from the GWN Series gas platform device.
4. Use the grooves on the sides of the AG01E to correctly position the sensor with respect to the GWN unit.
5. Press the connector block on the sensor onto the connector pins on the GWN unit.
Use these grooves to position the sensor
properly before pressing the sensor into the
pin connector on the GWN board.
6. The low relay setpoint value of the AG01E sensor is selectable (either 25 or 35 ppm). Use the setpoint selection switch on the
GWN board to choose LO (for 25 ppm) or HI (for 35 ppm).
The AG01E high setpoint value is fixed.
7. Replace the GWN front cover. Reconnect power.