INSTALLATION INFORMATION

CONDITIONS OF INSTALLATION

It is the law that all gas appliances are installed only by a competent (e.g. CORGI

Registered) Installer, in accordance with the installation instructions and the Gas

Safety (Installation and Use) Regulations 1998. Failure to install appliances

correctly could lead to prosecution. It is in your own interest and that of safety to

comply with the law.

The fire may be fitted below a combustible shelf provided that the shelf is at least

200mm above the top of the appliance and the depth of the shelf does not exceed

150mm.

The fire may be installed below combustible shelves which exceed 150mm deep

providing that the clearance above the fire is increased by 15mm for each 25mm

of additional overhang in excess of 150mm.

No purpose made additional ventilation is normally required for this

appliance when installed in G.B. When installed I.E. please consult

document I.S. 813 : 1996 Domestic Gas Installation which is issued by the

National Standards Authority of Ireland. Any purpose made ventilation

should be checked periodically to ensure that it is free from obstruction.

If the chimney or flue has been previously used by appliances burning fuels other

than gas they must be swept prior to the installation of this fire.

If this appliance is fitted directly on to a wall without the use of a fireplace or sur-

round, soft wall coverings such as wallpaper, blown vinyl etc. could be affected by

the heat and hot convection air and may discolour or scorch. This should be con-

sidered when installing or decorating.

The Model number of this appliance is as stated on the rating plate affixed to the

control panel of the fire and the appliance is manufactured by:-

BFM Europe Ltd

Trentham Lakes

Stoke on Trent

ST4 4TJ

2

Please Note : The life span of the batteries in the burner unit is dependent

upon use and therefore the battery life will vary accordingly. If the burner

unit fails to operate, please check the 6 off AA batteries before calling the

service centre for engineer assistance.

Содержание Orbis NVICC**MN

Страница 1: ...tructions should be read by the user before operating the appliance and retained for future reference Model No s NVICC MN NVICC SN NVICC RN are only for use on Natural Gas G20 at a supply pressure of...

Страница 2: ...I S 813 1996 Domestic Gas Installation which is issued by the National Standards Authority of Ireland Any purpose made ventilation should be checked periodically to ensure that it is free from obstruc...

Страница 3: ...ler and that during the service the fire is removed from the fire opening and the chimney or flue visually checked for fallen debris or blockages which must be removed The chimney should also be check...

Страница 4: ...ely event of a failure of the igniter the fire can be lit as follows Depress the control knob and turn anti clockwise to the position marked pilot Hold in the control knob for a few seconds to allow t...

Страница 5: ...the unlikely event of a failure of the igniter firstly check the operation of the 1 5V battery and if necessary replace with a AA size alkaline battery It is impor tant that only an alkaline battery...

Страница 6: ...o reduce the level of heat input on the fire point the handset at the fire and press the small flame button once An audible beep will be heard and the heat input level will reduce to the low setting 4...

Страница 7: ...will now remain in the off position until activated by the remote handset Fig 2 REPLACING THE BATTERIES REMOTE CONTROL MODELS ONLY ENSURE THE FIRE IS COOL BEFORE REPLACING BATTERIES Remove the ashpan...

Страница 8: ...re that the fire has been allowed to fully cool CLEANING THE TRIMS AND PAINTED METAL PARTS Dependent upon the trim option chosen for use with this fire there is a variety of methods that can be chosen...

Страница 9: ...uelbed base is located centrally in the fire box Ensure that the fuelbed base fit fully down onto the fuel bed support and is not lodged on the burner See fig 3 below Fig 3 b Position the two halves o...

Страница 10: ...ramic rail as a guide for placement See fig 5 below Fig 5 d Select two of the large square coals two of the large random coals and arrange behind the front row of coals ensuring that flame paths as in...

Страница 11: ...second row of coals using the ribs in the fuelbed matrix as a guide for placement See fig 7 below Fig 7 f Select the remaining two large square coals and two random coals and position to fill the gaps...

Страница 12: ...lled as RCF waste This is not classified as hazardous waste and may be disposed of at a tipping site licensed for the disposal of industrial waste Protective clothing is not required when handling the...

Страница 13: ...rts are as follows these are available from Verine Fires who may be contacted at the address shown on the rear cover Fuelbed base B 58690 Fuelbed front rails L H R H B 18730 Replacement coal set B 120...

Отзывы: