8.3
WV-11-04
Connections below show single phase with hydraulic thermostat.
Key
F1, F2
Fuses
FIL
Filter
SW
Instrument
Switch
C
Temperature
Controller
TC
Thermocouple
HT
Hydraulic
Thermostat
FA
Fault Light
SSR
Solid State Relay
EL
Element(s)
*
If Fitted
L
Live
N
Neutral
PE
(GR/Y)
Earth
(Green+Yellow)
Note on Hydraulic Thermostat: When used over 16 Amps or in a
2- or 3-phase model, the product is fitted with a contactor; with
the hydraulic thermostat in the coil circuit - similar to "WV-11-
01".
8.4
WS-02-02
Key
SW
Instrument Switch
FSC
Fan Speed Controller
FM
Fan Motor
L
Live
N
Neutral
The variable speed control is wired in series with the fan. The fan
activates when the instrument switch is turned on.
Control Circuit
26
Содержание CARBOLITE GERO WS-02-02
Страница 30: ......
Страница 31: ...Notes Service Record Engineer Name Date Record of Work ...