3.0 3216 Controller
Program Example
The following sequence of entries creates and runs the program shown graphically
below.
1. Press scroll
until the display shows RAMP.U <SP RAMP UNITS>. Select MIN.
2. Press scroll
until the display shows DWELL.U <DWELL UNITS>. Select MIN.
3. Press scroll
until the display shows RMP.1 <RAMP RATE 1>. Select 5
4. Press scroll
until the display shows T.SP1 <TARGET SP 1>. Select 600
5. Press scroll
until the display shows DWEL.1 <DWELL TIME 1>. Select 30
6. Press scroll
until the display shows RMP.2 <RAMP RATE 2>. Select 4
7. Press scroll
until the display shows T.SP2 <TARGET SP 2>. Select 400
8. Press scroll
until the display shows DWEL.2 <DWELL TIME 2>. Select 30
9. Press scroll
until the display shows RMP.3 <RAMP RATE 3>. Select OFF
10. Press scroll
until the display shows T.SP3 <TARGET SP 3>. Select 600
11. Press scroll
until the display shows DWEL.3 <DWELL TIME 3>. Select 60
12. Press scroll
until the display shows RMP.4 <RAMP RATE 4>. Select 3
13. Press scroll
until the display shows T.SP4 <TARGET SP 4>. Select 800
14. Press scroll
until the display shows DWEL.4 <DWELL TIME 4>. Select OFF
15. Press scroll
until the display shows RMP.5 <RAMP RATE 5>. Select 5
16. Press scroll
until the display shows T.SP5 <TARGET SP 5>. Select 400
17. Press scroll
until the display shows DWEL.5 <DWELL TIME 5>. Select 480
18. Press the ACK function to return to the home display.
19. Press the up
and down
keys together, to operate the program.