14
15
Thermostat Configuration
Configuring the Equipment Settings - Electric Heat
➤
Use the “Up” and “Down” buttons to change the Electric Heat setting
by changing the second digit;
0
No Electric Heat
1
*
Electric Heat
➤
Press the “Fan” button to advance to the next setting;
*
Indicates default setting;
ELECTRIC HEAT
Thermostat Configuration
Configuring the Equipment Settings - Reversing Valve
➤
Use the “Up” and “Down” buttons to change the Reversing Valve
setting by changing the third digit;
0
OB contact is energized to cool;
1
*
OB contact is energized to heat;
Refer to the HVAC unit documentation to determine the
correct OB VALVE setting.
If the incorrect OB VALVE Setting is selected, the HVAC unit
will turn on the heating when air conditioning is requested
and turn on the air conditioning when heating is requested;
➤
Press the “Fan” button to advance to the next setting;
➤
Press the “F/C” button to advance to the next menu;
*
Indicates default setting;
REVERSING VALVE