Verasys® 32 Point 24 VAC Application Controller Installation Instructions

23

Maximum Cable Length versus Load Current

Use Figure 12 to estimate the maximum cable length relative to the wire size and the load current (in mA) when 
wiring inputs and outputs.

Note:  

Figure 12 applies to low-voltage (<30 V) inputs and outputs only. Determine the required wire size and 

length for high-voltage (>30 V) relay outputs by the load connected to the relay and  local electrical codes.

Figure 12:   Maximum Wire Length for Low-Voltage (<30 V) Inputs and Outputs by Current and Wire Size

System/Sensor Bus and Supply Power Wiring Guidelines

Table 7 provides information about the functions, ratings, and requirements for the communication bus and supply 
power terminals. Table 5 also provides guidelines for wire sizes, cable types, and cable lengths when wiring the 
controller's communication buses and supply power. In addition to the guidelines in Table 7, use these guidelines to 
wire a Sensor or System bus and the 24 VAC supply power:

Run all low-voltage wiring and cables separate from high-voltage wiring.

All Sensor and System bus cables, regardless of wire size, must be twisted, insulated, stranded copper wire.

Using shielded cable is best practice for all Sensor and System bus cables.

B

1.5 mm

(32 AWG) 

stranded copper

229 m (750 ft) twisted 
wire

100 mV maximum voltage drop.
Depending on the cable and the connected input or 
output device, you may have to define an offset in the 
setup software for the input or  output point.

0.8 mm

2

 (20 AWG) 

stranded copper

137 m (450 ft) twisted 
wire

0.6 mm

2

 (22 AWG) 

stranded copper

91 m (300 ft) twisted 
wire

N/A (24 AWG) 
stranded copper

61 m (200 ft) twisted 
wire

C

See Figure 12 to 
select wire size/
gauge. Use stranded 
copper wire.

See Figure 12 to 
determine cable length. 
Use twisted wire cable.

N/A

Table 6:  Cable Length Guidelines for Wire Sizes for Low-Voltage (<30 V) Inputs and Outputs (Part 2 of 2)

Guidelines

Wire Size/Gauge and 
Type

Maximum Cable 
Length and Type

Assumptions

450

500

400

350

300

250

200

150

100

50

0

0 m  0 ft

(

)

15.2 m  50 ft

(

)

30.5 m  100 ft

(

)

45.7 m (150 ft)

61 m  200 ft

(

)

76.2 m  250 ft

(

)

91.4 m  300 ft

(

)

106.7 m  350 ft

(

)

121.9 m  400 ft

(

)

137.2 m  450 ft

(

)

Load Current (mA)

Length

1.5 mm  (18 AWG)

2

0.8 mm (20 AWG)

0.6 mm (22 AWG)

N/A (24 AWG )

Содержание LC-VAC300 0 Series

Страница 1: ...e devices and remote connectivity Verasys Smart Building Hub SBH compatible through the BACnet MSTP system bus connection Dedicated Sensor bus for Johnson Controls smart end devices Dedicated Modbus p...

Страница 2: ...the ambient condition requirements listed in Table 11 Ensure sufficient space around the controller for cable and wire connections for easy cover removal and good ventilation through the controller Pr...

Страница 3: ...field controller horizontally on 35 mm DIN rail is the preferred mounting method To mount a field controller on 35 mm DIN rail complete the following steps 1 Securely mount a 20 cm 8 in or longer sect...

Страница 4: ...Verasys 32 Point 24 VAC Application Controller Installation Instructions 4 Figure 2 Back of Controller Showing Extended Mounting Clips DIN Rail Channel and Mounting Dimensions mm in...

Страница 5: ...her aucune partie du circuit imprim lorsque celui ci est sous tension Le non respect de ces pr cautions peut provoquer des blessures graves voire mortelles Risk of Electric Shock Disconnect or isolate...

Страница 6: ...Table 5 and use a spade connector with screw terminals Figure 3 shows I O spade terminals Figure 3 Verasys Application Controller Spade Terminals Field Wiring For all I O terminals listed in Table 5 u...

Страница 7: ...the other field controllers in a daisy chain configuration using 3 wire twisted shielded cable as shown in the following figure See Table 7 for more information on functions ratings requirements and...

Страница 8: ...cts internally to the Sensor bus terminal block See Table 7 for more information The sensor bus port pin assignment is shown in Figure 8 Figure 8 Pin Number Assignments for Sensor Bus Ports on Verasys...

Страница 9: ...ne to many Modbus devices Each Modbus device has a unique Modbus Register table and you must configure it within the application of the Verasys Controller Figure 9 Modbus Terminal Block COM Cable Shie...

Страница 10: ...ngs for wiring details EOL Switch The red end of line switch EOL is located under the cover of the controller You can set the red EOL switch when the device is located at the end of the trunk or at th...

Страница 11: ...ut power for actuator supply 7 24 VAC class 2 power supply terminal block See the Supply Power Terminal Block section 8 Cover lift tabs 9 Sensor Bus Port RJ 12 6 pin Modular Jack See Sensor Bus Port s...

Страница 12: ...ype of Field Device Type of Input Output Termination Diagrams Resistive Input resistance temperature detector RTD Monitor UI Voltage Input External Source UI Voltage Input Internal Source UI Voltage I...

Страница 13: ...k from EPP 100 UI Dry Contact Binary Input UI BI Table 2 Termination Details Part 2 of 6 Type of Field Device Type of Input Output Termination Diagrams Controller FIELD DEVICE VDC Output 15V IN IN ICO...

Страница 14: ...e V e r a s y s 2 4 V A C S u p p ly a r e b o th g r o u n d e d to F u n c tio n a l E a r th e n s u r e th a t th e p h a s in g b e tw e e n th e tw o s u p p lie s a r e a lig n e d H O T Common...

Страница 15: ...f Input Output Termination Diagrams Common Power Calibration Output Current Input Voltage Input Feedback Terminal Block 1 1 2 3 4 5 6 OCOM OUT Controller 24 VAC COM 24 VAC HOT 24VAC Load OUT OCOM CONT...

Страница 16: ...and BO 7 Hardware Interlock Relays BO See Table 3 for Selectable Operating Modes Table 2 Termination Details Part 5 of 6 Type of Field Device Type of Input Output Termination Diagrams 240VAC Load OUT...

Страница 17: ...ing BO Relay 6 Open Short BO Relay 6 energizes when BI11 is Active 24 VAC present on BI11 7 J2 1 and J2 2 J2 2 and J2 3 Open Open BO Relays 7 remains de engerized in default state NO cannot be control...

Страница 18: ...ring and cables separate from high voltage wiring All input and output cables regardless of wire size or number of wires must consist of stranded insulated and twisted copper wires Shielded cable is n...

Страница 19: ...INn terminals provides 80 mA total current Note 80mA current limit is shared between the BI 15V supply and the UI 15V supply Same as Universal INn INn Analog Input Voltage Mode 0 10 VDC 10 VDC maximum...

Страница 20: ...al Mode 24 VAC Input Present Logic 1 Active ICOMn Binary Input Common for all Binary Input IN terminals 15 V 15 VDC Power Source for active 3 wire input devices connected to the Universal INn terminal...

Страница 21: ...Resistive 3A Inductive Cos phi 0 6 20 to 70 C 4 to 158 F 100K cycles The RELAY output terminals can accommodate the following maximum wire sizes Two wires per terminal 1 5 mm2 16 AWG maximum or One w...

Страница 22: ...y Commons Note Reference all relay commons to the same pole of the supply circuit PWM Output OUT5 PWM PWM Output User selectable PWM output voltage 5V 12V default and 15V 10 mA continuous current 100...

Страница 23: ...low voltage wiring and cables separate from high voltage wiring All Sensor and System bus cables regardless of wire size must be twisted insulated stranded copper wire Using shielded cable is best pra...

Страница 24: ...Signal Reference and 15 VDC Common 15 VDC 71 5 ohms at 4 W N A 24 AWG 3 pair CAT3 cable 30 5 m 100 ft Sensor Bus Terminal Lower Sensor Bus Communications 0 6 mm2 22 AWG stranded 4 wire 2 twisted pairs...

Страница 25: ...ces Not for use on field controllers 117 Reserved for SBH 4 to 127 Used for MS TP devices also known as field controllers that are hardwired to a Sensor and System bus Table 9 Status LEDs and Descript...

Страница 26: ...ted to Binary Outputs BOs or Configurable Outputs COs This can consume up to 12 VA for each BO or CO for a possible total consumption of an additional 60 VA maximum Ambient Conditions Operating 20 C t...

Страница 27: ...0 mV accuracy in 0 to 10 VDC applications Terminations Input Output Fixed Spade terminals Sensor System Modbus 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Sensor Bus Tool Port RJ 12 6 Pin Modula...

Страница 28: ...f their respective owners 2018 Johnson Controls www johnsoncontrols com 28 European Single Point of Contact NA SA Single Point of Contact APAC Single Point of Contact JOHNSON CONTROLS WESTENDHOF 3 451...

Отзывы: