12
VUT/VUE 550/900 PBW EC
www.ventilation-system.com
DISCONNECT THE UNIT FROM POWER
SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER MAINS BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE
MANUFACTURER'S LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED
AND WILL VOID THE WARRANTY.
The unit is rated for connection to 230 V/50 (60) Hz single-phase alternating current power mains via insulated, durable and thermal-
resistant cords (cables, wires) with respective cross section not less than 2.5 mm
2
. The cable cross-section is given for reference only. The
applicable cable cross section must be selected depending on the wire type, its maximum temperature and insulation, the maximum
current, the wire length and its installation method. Connect the unit to power mains through the external automatic circuit breaker with
a magnetic trip integrated into the fixed wiring system with the rated current not below the rated current consumption.
The terminal block with the prewired control unit is located inside the control unit compartment.
To connect the power and the ground cable, route the cables through the airtight electric lead-in in the unit casing and connect these
to the terminal block.
The wiring diagram for connection of the air handling unit to power supply is on the back side of the lid.
CONNECTION TO POWER MAINS
EXTERNAL CONNECTIONS DIAGRAM OF A21
NO
C
C NO C NO
B
A Gnd +24V 0-10V Gnd C NO C NC C NC In Gnd 0-10V Gnd +24V N
L
30
31
29 28 27 26
25 24 23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
L1
N
+24V
CCU*
2 1
SM2*
2 1
SM1*
U**
U**
+24V B A Gnd
Р
1*
+24V0-10V Gnd
C
О
2*
2 1
Boost*
2 1
PK1*
2 1
2 1
0-24V
SM3*
2 1
M3*
DD1*
BP1*
U**
U**
~230 VAC
50/60 Hz
Gr
een
Br
own
Yello
w
W
hit
e
Designation
Name
Model
Wire***
Note
M3*
Circulation pump
2 x 0,75 мм
2
SM3*
Three-way valve electric actuator
3 x 0,75 мм
2
BP1*
Heating medium flow control sensor
NC
2 x 0,75 мм
2
DD1*
Heating medium pressure switch
NC
2 x 0,75 мм
2
remove the jumper
РК1
*
Contact from fire alarm panel
NC
2 x 0,75 мм
2
remove the jumper
Boost
*
On/Off contacts of the Boost mode
NO
2 x 0,75 мм
2
CO
2
*
External CO
2
sensor
3 x 0,75 мм
2
Р1
*
External control panel
4 x 0,25 мм
2
SМ1
*
Supply air damper actuator
NO
2 x 0,75 мм
2
3 A, 30VDC/~250 AC
SМ2
*
Exhaust air damper actuator
NO
2 x 0,75 мм
2
3 A, 30VDC/~250 AC
CCU
*
Cooler control
NO
2 x 0,75 мм
2
3 A, 30VDC/~250 AC
*Is not included in the delivery set.
**The supply voltage U of the SM1, SM2 external dampers is selected depending on the type of dampers.
*** Maximum connecting cable length is 20 m!
Output parameters: terminals 26-31 – 3 A, 30VDC/~ 250VAC (“dry contact”).
— ELECTRIC SHOCK HAZARD!
Содержание VUE 550 PBW EC
Страница 1: ...VUT VUE 550 PBW EC VUT VUE 900 PBW EC Heat and energy recovery air handling unit USER S MANUAL ...
Страница 17: ...17 www ventilation system com VUT VUE 550 900 PBW EC ...
Страница 18: ...18 VUT VUE 550 900 PBW EC www ventilation system com ...
Страница 19: ...19 www ventilation system com VUT VUE 550 900 PBW EC ...
Страница 20: ...V217 1EN 02 ...