12
VUT/VUE HB(E) ЕС
www.ventilation-system.com
Wiring diagram
(unit with an A14 controller)
SM1*
2
1
SM2*
2
1
PK1*
1
2
CO2*
1
2
RH*
+U
Rx
Tx
GND
P1
X1
16 17
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
L
N
+U
Rx
Tx
GND
C
NO
GND
0-10V
+U
C
NC
PE
N
L
0-10V
GND
+U
HV2*
~230 VAC
L
N PE
QF*
XP*
Designation
Unit name
Cable type
Maximum cable
length
Note
SМ1*
Supply air damper actuator
2x0.75 mm
2
20 m
SМ2*
Extract air damper actuator
2x0.75 mm
2
20 m
РК1*
Contact from a fire alarm panel
2x0.75 mm
2
20 м
Remove the jumper during installation
Р1
Control panel
4x0.25 mm
2
10 m
CO2*
or
RH*
CO₂ concentration and indoor humidity sensor
HV2*
Humidity sensor in the exhaust air duct inside the unit
XP*
Electric plug
QF*
Automatic circuit breaker
X1
Terminal block
Wiring diagram
(
unit with an A21 controller
)
Boost
Kamin
X1
X3
QF*
XP*
CCU*
PK1*
1
2
+24V
B
A
GND
P1*
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
C
NO
C
NO
C
NO
+24V
B
A
GND
C
NO
C
NO
C
NC
PE
N
L1
PE
N
L
~230 VAC
L
N PE
SM1*
2
1
SM2*
2
1
U
U
Designation
Unit name
Cable type
Maximum cable
length
Note
CCU*
Compressor-condenser unit
2x0.75 mm
2
20 m
3 A. 30 DC/~250 AC
SМ1*
Supply air damper actuator
2x0.75 mm
2
20 m
3 A. 30 DC/~250 AC
SМ2*
Extract air damper actuator
2x0.75 mm
2
20 m
3 A. 30 DC/~250 AC
РК1*
Contact from a fire alarm panel
2x0.75 mm
2
20 m
Р1*
Control panel
4x0.25 mm
2
10 m
HV2*
Humidity sensor in the exhaust air duct inside the unit
XP*
Electric plug
QF*
Automatic circuit breaker
X1. X3
Terminal blocks
Boost
Contact on/off. Boost mode
Kamin
Contact on/off. Kamin mode
*Additionally connected devices are purchased separately. The connection must be made using durable. insulated and heat-resistant
conductors (cables. wires). Requirements to a connection cable are shown in the table.