9
www.ventilation-system.com
Reference dimensions for installation of
ventilators
Ventilator model or installation variant
TwinFresh Style mini
TwinFresh Style
TwinFresh Style
with minimum wall
thickness
Length of cartridge or fan and
regenerator units [mm]
165
370
310
Hole diameter D [mm]
120
180
180
Minimum possible wall thickness when
using EH, EH-14, EH-13, EH-17, MVVM
hoods (mm)
from 155
from 360
300
Minimum possible wall thickness when
using an EH-2 hood (mm)
from 55
from 260
200
1. Prepare a round core hole in the outer wall.
The figure below shows the minimum distance from the hole to the surrounding objects.
The hole diameter depends on the specific ventilator model. The corresponding values are given in the table.
A
A
A-A
ø D
min 300
min 300
min 300
2. Insert the air duct in the wall. For ease of installation use the mounting wedges included in the delivery set.
The air duct end must protrude for the distance A that enables installation of the outer ventilation hood. The overall dimensions of
the outer ventilation hood, the outside protrusion length of the air duct A and the mounting sequence of the hood are stated in its
installation instruction.
A
min 3 mm
Fill the gaps between the wall
and the hole with a mounting
foam.
Mounting wedge
Install the air duct with the minimum slope of 3 mm downwards
from the outer wall side.
The air duct can be cut by calculating preliminary the required
length or after fixing the air duct on the wall (in this case, it is
necessary to have access to the outside part of the wall).
3. Install the outer ventilation hood. The mounting sequence of the outer ventilation hood is described in the installation instruction for
the ventilation hood.