Vents RNS-16 Скачать руководство пользователя страница 10

10

 

MOUNTING AND SET-UP

Controller circuit board functional outputs: 

 1 - Internal or external 0-10 V control input 

selection; 

 2 - Control mode selection;

 3 - Cycle length adjustment resistor (factory set);

 4 - TRIAC operation indicator; 

 5 - Heating cascade 1 indicator; 

 6 - Heating cascade 2 indicator ;

 7 - Heating cascade 3 indicator;

 8 - Terminal block for temperature sensor 

connection;

 9 - Terminal block for external 0-10 V control 

input; 

 10 - Terminal block for protection and enabling 

contacts;

 11 - Control circuit board fuse; 

 12 - Operation indication relay:  

NO - Alarm or no enabling signal; 

NC - Unit operation. 

Jumper 1

External 0-10 V control input

Integral 0-10 V pot resistor

Jumper 2

Temperature sensor feedback 

mode using three cascades

Temperature sensor feedback 

mode using cascade 1

Heating power output maintenance 

mode using cascade 1 

Heating power output maintenance 

mode using three cascades 

in

11

12

9

K2

14

PT+

8

15

GND

7

18

GND

19

IN1

5

PD

1

21

TK50

22

RB

25

3

1

Q3

Q1

CQ

DO2

PE

Tset

out

10

K3

13

GND

PTin

6

K1

SC

R

16 17

Tset

+10 V

4

RA

TK50

PD

1

23

24

20

L

N

2

Q2

DO1

DO1

DO2

C2

C4

VD10

C7

VD6 VD7 VD8 VD9

DA1

X11

C8

C9

C10

ICSP

R5

R1

X6

X2

R3

R4

X9

X1

C5

DA2

X14

K3

U4

U2

C1

R7

R8

R9

X3

X4

R2

R73

C3

Z1

X5

X8

C6

DA3

X10

K2

K4

U3

U1

T1

R6

K1

X12 X13

9

3

2

8

10

1

12

11

7 6 5 4

F1

500 mA 

Содержание RNS-16

Страница 1: ...USER S MANUAL TRIAC POWER CONTROLLER FOR ELECTRIC HEATERS RNS 16 RNS 25...

Страница 2: ...cal data 6 Design and operating principle 8 Mounting and set up 10 Connection to power mains 12 Technical maintenance 17 Transportation and storage regulations 17 Manufacturer s warranty 18 Acceptance...

Страница 3: ...o follow the rules and safety precautions noted in this user s manual may result in an injury or unit damage After a careful reading of the manual keep it for the entire service life of the unit While...

Страница 4: ...isconnect it from power supply and contact the Seller Do not open the unit during operation In case of continuous operation of the unit periodically check the security of mounting Do not sit on the un...

Страница 5: ...NG THE APPROPRIATE TRAINING THE CONTROLLER MUST BE HANDLED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS...

Страница 6: ...modes 1 Maintaining the pre set duct temperature according to the duct temperature sensor feedback 2 Regulation of the heating output within the 0 to 100 range by using the 0 10 V control input The co...

Страница 7: ...10 Protection class IP54 Outside dimensions mm 170x255x140 Weight kg 1 2 Electric mains parameters Voltage V Frequency Hz Phases 210 255 380 415 50 60 1 or 3 Operating temperature range C 5 40 Note In...

Страница 8: ...en increased to the required level to ensure reaching the target temperature To connect two extra heating cascades install an electric contactor for activating each heater cascade For overheating prot...

Страница 9: ...back operation ON BLINKING Temperature boosting T set T flow ON ON Reaching mode parameters T set T flow Power output mode ON BLINKING The blinking frequency is proportional to the power supplied to t...

Страница 10: ...Alarmornoenablingsignal NC Unitoperation Jumper 1 External 0 10 V control input Integral 0 10 V pot resistor Jumper 2 Temperature sensor feedback mode using three cascades Temperature sensor feedback...

Страница 11: ...controller front lid If necessary disconnect the flexible flat cable Connect the controller to the electric mains according to the connections diagram Route the electric power cables into the casing t...

Страница 12: ...ly fan pressure switch Single phase mains connection Three phase network connection Electrical connections diagrams To enable several heating cascades install a dedicated electric contactor for each h...

Страница 13: ...K1 1 K1 3 K1 2 90 C 50 C Supply fan pressure switch Temperature sensor R85 1 2 N L1 L2 L3 400 V QF1 Heating element 3 Heating element 2 Heating element 1 CONTROLLER CIRCUIT BOARD 10 V 0 10 V Gnd Gnd...

Страница 14: ...K2 2 K1 1 K1 2 90 C 50 C 1 N L 230 V QF1 10 V 0 10V Gnd Gnd VD1 VD2 VD3 HL1 HL3 HL2 SB X8 X9 X10 RB RA TK50 TK50 PT in PT Gnd X5 Test 10 V Gnd X6 PD1 In 1 PD1 Gnd Start Supply fan pressure switch Tem...

Страница 15: ...DO2 K1 K1 1 K1 3 K1 2 90 C 50 C R85 1 2 N L1 L2 L3 QF1 10 V 0 10V Gnd Gnd VD1 VD2 VD3 HL1 HL3 HL2 SB X8 X9 X10 RB RA TK50 TK50 PT in PT Gnd X5 Test 10 V Gnd X6 PD1 In 1 PD1 Gnd Start Supply fan pressu...

Страница 16: ...O1 DO2 DO2 K1 K1 1 K1 2 90 C 50 C R85 1 N L 230 V QF1 10 V 0 10V Gnd Gnd VD1 VD2 VD3 HL1 HL3 HL2 SB X8 X9 X10 RB RA TK50 TK50 PT in PT Gnd X5 Test 10 V Gnd X6 PD1 In 1 PD1 Gnd Start Supply fan pressur...

Страница 17: ...liminate the factors preventing proper air cooling of the heating element Controller malfunction Temperature sensor malfunction Replace the temperature sensor Incorrect operating mode selection Check...

Страница 18: ...The warranty repair shall include work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation The faults are eliminat...

Страница 19: ...ations Unit connection to the power mains with a voltage different from the one stated in the user s manual Unit breakdown due to voltage surges in the power mains Discretionary repair of the unit by...

Страница 20: ...08 EC 89 336 EEC and Low Voltage Directive 2006 95 EC 73 23 EEC and CE marking Directive 93 68 EEC on the approximation of the laws of the Member States relating to electromagnetic compatibility This...

Страница 21: ...ate Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and standards The unit operates normall...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...V116 2EN 03...

Отзывы: