Vents PU JK 01 Скачать руководство пользователя страница 8

8

PU JK

PU JK

14. Humidity Feedback Control Activation.

To enable humidity feedback control enter the service menu and use the 

 button to 

select the humidity feedback control activation mode. While in the humidity feedback 

control activation mode the 

 and 

 indicators on the control panel display are 

blinking. Then press the 

 button to enter the humidity feedback control activation 

mode. 

Use the 

 and

 

 

 buttons to set the value:

 — Disabled (Default). 

     — Enabled. 

ERROR 

CODE 

HEATER TYPE

ELECTRIC

WATER

00

Control panel connection error.

01

Outdoor temperature sensor failure.

02

Heat exchanger freeze protection sensor malfunction.

03

Return heat medium temperature sensor malfunction.

04

Heater freeze temperature sensor malfunction.

05

Duct temperature sensor malfunction.

06

Duct humidity sensor malfunction.

07

Supply fan malfunction.

08

Extract fan malfunction.

09

Electric heating element overheating (TK50). 

10

Fire alarm sensor is activated.  

11

TK-90 overheat sensor is activated.

13

Insuffi

  cient operational water pressure indication.

Note: when suffi

  cient water pressure is present the unit is switched on automatically.

Contact the unit seller to resolve the alarm.

15. Error codes.

In case of an emergency the unit switches off  while the alarms are displayed on the control panel 

display screen: the fl ashing indicator 

and the error code indicator that indicates the error cause. 

Error codes and their description are shown in the table below.

Error code

Alarm

Содержание PU JK 01

Страница 1: ...USER S MANUAL PU JK 01 LCD Control Panel...

Страница 2: ...to every installation or repair operation The control panel must not be operated outside the temperature range stated in the user s manual or in aggressive or explosive environments Do not position an...

Страница 3: ...included in the delivery PARAMETER VALUE Ambient Temperature C From 5 to 40 Relative Humidity From 5 to 80 no condensation Recommended cable cross section mm2 0 22 0 25 Material Plastic Dimensions W...

Страница 4: ...r lights up when the bypass opens Timer status the indicator lights up when the timer is activated the indicator glows when the timer is off Heater status the indicator glows while the heater is on 1...

Страница 5: ...buttons to set the heater status the indicator is blinking fast the heater is off the indicator is blinking slowly the heater is on From the remote control press the button to switch the heater on pr...

Страница 6: ...e by means of the and buttons The date and time parameters appear in the following order Minutes Hours Day of the Week Date Month 6 Timer On Off The timer is used to switch the fans to the speed defin...

Страница 7: ...on to select the reset to factory settings mode While in the reset to factory settings mode the and the indicators on the control panel display are blinking Then press the button to enter the Reset to...

Страница 8: ...urn heat medium temperature sensor malfunction 04 Heater freeze temperature sensor malfunction 05 Duct temperature sensor malfunction 06 Duct humidity sensor malfunction 07 Supply fan malfunction 08 E...

Страница 9: ...ature 10 30 User defined Temperature in the Standby Mode 20 29 Air Flow at Low Speed in Air Extract Mode 0 99 Air flow in the exhaust air duct at low speed defined as a percentage of the maximum unit...

Страница 10: ...V55 5EN 02 1...

Отзывы: