Model
PА 01 Е
PА 02 Е
PА 03 Е
Supply Voltage, V/50 Hz
3 ~ 400
Maximum Fan Power, W
320
620
1330
Fan Current, A
0,55
1,05
2,4
Electric Heater Power, kW
12,0
18,0
21,0
Electric Heater Current, A
17,4
26,0
30,0
Total Unit Power, kW
12,4
19,0
22,4
Maximum Unit Current, A
18,0
27,1
32,4
Maximum Air Flow, m
3
/h
1275
2500
3350
Rotation speed, min
-1
2700
2690
2730
Sound Pressure Level at 3m. , dB(A)
51
54
57
Maximum Transported Air Temperature, °C at T
from -25 to + 55
from -25 to + 45
Casing Material
Aluzinc
Insulation
50 mm, mineral wool
Filter
Panel type G4
Connected duct size, mm
400х200
500х300 600х350
Weight, kg
56
61
91
Table. 2 . Unit Technical Parameters
SAFETY REQUIREMENTS
While operating and mounting the unit consider the requirements of the present operation manual
as well as general requirements of all applicable local and national building and electrical codes and
standards.
The unit must be properly earthed!
Before connecting the unit to power mains make sure that the unit is free of any visible damages or
any other foreign objects inside the casing that can damage the impeller blades. Otherwise contact the
service center.
Warning!
Disconnect the unit from power supply prior to any mounting, servicing, connection
or repair operations with the unit.
Do not!
•
Do not operate the unit beyond the specified temperature range or in an aggressive
and explosive medium!
•
Do not connect clothes dryers or similar equipment to the ventilation system!
•
Do not operate the unit in the air and dust mixture medium!