NK…U

CONTROL

Connection of NK…U, NK…Un with capacity from 0.6 kW to 2.4 kW  

with integrated temperature control module for round air ducts 

Use the temperature control knob to set the desired temperature in the air duct (thermostat operation threshold). The temperature can be set in the 
range from -10 °C to +40 °C.  
The heater switches on automatically upon the air temperature dropping below the preset thermostat operation threshold.
When the air warms up to the preset level the heater switches off automatically.  

NK…U with capacity from 3.0 kW to 54.0 kW  

with a control unit for round and rectangular air ducts

Complete the electrical connections according to the respective diagram, see page 18.
To use the temperature sensor feedback connect the sensor to the 

X2

 terminal block. 

TE1 [Gnd. PTin. PT+]

•  PT+

 – sensor power – „brown“

•  Gnd

 – analogue ground contact – „shield“ 

•  PTin

 – sensor signal input – „white“

Jumper 1

 (see page 14) sets the heater control method using signals of the external temperature set-point adjuster (the 0–10 V controller) or the 

feedback from the built-in temperature controller. To use the feedback from an external control device connect it to the 

X2

 terminal block. 

Control [GND. 0–10 V]

.

•  GND

 – analogue ground contact

•  0–10 V 

– set-point adjuster input

Protective contact circuit connection.
The „Start“ signal (the activation signal source device) must be connected to the 

X2

 terminal block: Enable 

[no and s];

The flow sensing element (the supply filter pressure switch) must be connected to the 

X2

 terminal block: 

PD1 [no and s].

Supply the power voltage to the unit and activate the heater by pressing the ON/OFF button. Then use the controller knob connected to the 
potentiometer to set the desired temperature in the range from -30 °C to +30 °C.
The NK...U heaters equipped with a control unit have one or several power relays depending on the number of the controlled cascades in use. The relays 
are connected to the controller circuit board via the TK 90 protective thermal contact at the factory.

External wiring diagram

1

2

3

4

5

6

7

8

9

X2

Thermoresistor

External 

temperature 

set point adjuster Air flow 

sensor

„Start” 

signal

tE

TE1

Control

PD1

Enable

GND PTin PT+ GND 0-10В no

c

no

c

0–10 V 

controller

Gnd Out E+

shield

whit

e

br

own

TECHNICAL MAINTENANCE

THE UNIT TECHNICAL MAINTENANCE MUST BE PERFORMED BY ADEQUATELY QUALIFIED AND 

TRAINED PERSONNEL UPON UNIT DISCONNECTION FROM THE POWER MAINS.

The heater maintenance includes:
Inspection of screw connections as well as rivet and welded joints.
Inspection of tightening of ground screw clamps and electric connections.
Inspection of the wire terminal connections.
Cleaning of the electric heating elements of dust and dirt. 
Cleaning with solvents or flammable substances is not allowed.

Содержание NK 100-0.6-1 U

Страница 1: ...USER S MANUAL Air duct heater with an integrated temperature control module or a control unit NK U...

Страница 2: ...ater or the unit as mentioned in the Safety requirements and Manufacturer s warranty sections as well as in warnings and information blocks SAFETY REQUIREMENTS Read the user s manual carefully prior t...

Страница 3: ...et hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit Disconnect the unit from power mains prior to any tec...

Страница 4: ...ithout disconnection from the power mains Transported air must not contain any flammable or explosive mixtures evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil par...

Страница 5: ...tem x 0 8 NK 100 1 2 1 U Un 90 5 2 230 2 items x 0 6 NK 100 1 6 1 U Un 120 7 0 230 2 items x 0 8 NK 100 1 8 1 U Un 130 7 8 230 3 items x 0 6 NK 125 0 6 1 U Un 60 2 6 230 1 item x 0 6 NK 125 0 8 1 U Un...

Страница 6: ...50 14 8 230 2 items x 1 7 NK 160 3 6 3 U 265 5 2 400 3 items x 1 2 NK 160 5 1 3 U 375 7 4 400 3 items x 1 7 NK 160 6 0 3 U 440 8 7 400 3 items x 2 0 NK 200 3 4 1 U 250 14 8 230 2 items x 1 7 NK 200 3...

Страница 7: ...0x300 10 5 3 U 770 15 2 400 10 5 3x4 0 NK 500x300 12 0 3 U 880 17 4 400 12 0 3x5 0 NK 500x300 15 0 3 U 1100 21 7 400 15 0 3x6 0 NK 500x300 18 0 3 U 1320 26 0 400 18 0 3x7 0 NK 500x300 21 0 3 U 1540 30...

Страница 8: ...126 230 370 290 1 8 NK 125 2 4 1 U Un 124 126 230 454 374 2 NK 150 1 2 1 U Un 149 144 255 306 226 2 1 NK 150 1 7 1 U Un 149 144 255 306 226 2 1 NK 150 2 0 1 U Un 149 144 255 306 226 2 1 NK 150 2 4 1 U...

Страница 9: ...K 160 3 4 1 U 159 187 350 370 298 4 6 NK 160 3 6 3 U 159 187 350 370 298 5 2 NK 160 5 1 3 U 159 187 350 370 298 5 2 NK 160 6 0 3 U 159 187 350 370 298 5 2 NK 200 3 4 1 U 199 237 389 376 298 5 2 NK 200...

Страница 10: ...0 520 702 250 270 290 228 23 0 NK 500x250 10 5 3 U 500 520 702 250 270 290 228 23 0 NK 500x250 12 0 3 U 500 520 702 250 270 290 228 23 0 NK 500x250 15 0 3 U 500 520 702 250 270 290 228 23 1 NK 500x250...

Страница 11: ...370 390 228 28 5 NK 600x350 24 0 3 U 600 620 802 350 370 390 228 28 5 NK 700x400 18 0 3 U 700 720 924 400 420 440 410 16 8 NK 700x400 27 0 3 U 700 720 924 400 420 440 530 21 0 NK 700x400 36 0 3 U 700...

Страница 12: ...c thermostat control knob with a temperature scale The rear panel of the junction box has sealed lead ins for leading the power cable grounding conductor and the remote temperature sensor cable The he...

Страница 13: ...ding on the pre programmed heating requirements For example if the full load is intermittently on and off in 5 second periods the heater runs at 50 of its maximum power output The cycle time i e the t...

Страница 14: ...GND 19 IN1 5 PD1 21 TK50 22 RB 25 3 1 Q3 Q1 CQ DO2 PE Tset out 10 K3 13 GND PTin 6 K1 SCR 16 17 Tset 10 V 4 RA TK50 PD1 23 24 20 L N 2 Q2 DO1 DO1 DO2 C2 C4 VD10 C7 VD6 VD7 VD8 VD9 DA1 X11 C8 C9 C10 I...

Страница 15: ...ouble the connection size No inflammable explosive or fire hazardous materials are allowed within 150 mm of the heater casing and within 500 mm of the heater air inlet and outlet Air ducts and fans mu...

Страница 16: ...ent must be consistent with the maximum current consumption of the unit The recommended nominal trip current of the circuit breaker the cross section and the number of cores are given in the respectiv...

Страница 17: ...3x2 5 NK 125 0 6 1 U Un 230 3 15 3x0 75 NK 125 0 8 1 U Un 230 4 0 3x0 75 NK 125 1 2 1 U Un 230 6 3 3x2 5 NK 125 1 6 1 U Un 230 8 0 3x2 5 NK 125 2 4 1 U Un 230 10 0 3x2 5 NK 150 1 2 1 U Un 230 6 3 3x2...

Страница 18: ...ge V Rated current of the circuit breaker A Number of cores cross section mm2 NK 150 3 4 1 U 230 20 3x2 5 NK 160 3 4 1 U 230 20 3x2 5 NK 200 3 4 1 U 230 20 3x2 5 NK 250 3 0 1 U 230 20 3x2 5 NK 150 3 6...

Страница 19: ...3 U 400 10 5x2 5 NK 500x300 7 5 3 U 400 16 5x2 5 NK 500x300 9 0 3 U 400 16 5x2 5 NK 500x300 10 5 3 U 400 20 5x2 5 NK 500x300 12 0 3 U 400 20 5x2 5 NK 500x300 15 0 3 U 400 25 5x2 5 NK 500x300 18 0 3 U...

Страница 20: ...ut Protective contact circuit connection The Start signal the activation signal source device must be connected to the X2 terminal block Enable no and s The flow sensing element the supply filter pres...

Страница 21: ...mantling unit setup To benefit from warranty repair the user must provide the unit the user s manual with the purchase date stamp and the payment document certifying the purchase The unit model must c...

Страница 22: ...ail Purchase Date This is to certify acceptance of the complete unit delivery with the user s manual The warranty terms are acknowledged and accepted Customer s Signature Seller s Stamp INSTALLATION C...

Страница 23: ......

Страница 24: ...V09 2EN 06...

Отзывы: