CONNECTION TO POWER MAINS
DISCONNECT THE UNIT FROM POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE POWER MAINS CONNECTION SHALL ONLY BE PERFORMED BY A QUALIFIED
ELECTRICIAN WHO IS AUTHORIZED FOR UNASSISTED OPERATIONS WITH ELECTRIC UNITS
OF POWER VOLTAGE UP TO 1000 V AFTER CAREFUL STUDY OF THE USER’S MANUAL.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S
LABEL. ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE
WARRANTY.
The units are designed for connection to AC 230 V/50 Hz single- or 400 V / 50 Hz three-phase power mains depending on the unit type. The
cable cross section must be in compliance with the unit power consumption, wire type, maximum heating temperature, insulation type, cable
length and installation type.
Use cables with copper wires only!
The unit is connected to power supply on the terminal block according to the wiring diagram and terminal marking. Connect the control and
power cables in compliance with the terminal marking and polarity.
Connection to power mains must be performed via an automatic circuit breaker with magnetic trip, integrated into fixed house cabling with
the tripping current exceeding the unit current consumption.
EXTERNAL WIRING DIAGRAM FOR THE MPA 800 W, MPA 1200 W, MPA 1800 W AND MPA 2500 W UNITS
Freemax MX
L N PE 1
L
2
N
3
PE
4
PE
5
N
6
L
7
1
8
2
9
c
10
no
11
nc
12
c
13
no
14
1
15
2
16
3
17
6
18
5
19
1
20
9
21
2
22
3
23
4
24
7
25
1
26
2
27
1
28
2
29
1
30
2
31
1
32
1
ALP
Cooler ac
tiv
ation sig
nal
(NO c
on
tac
t)
9
1
5
6
7 8
4
3
2
P1*
1
2
PK1*
AI1
AI3
AI4
AIgnd
AI5
AIgnd
DIgnd
DI8
DI3
AI7
DO1
DO2
DO4
DI1
DI2
DIgnd
AI6
AO3
24V AC
~
2
1
DD1*
1
3
2
PD1
1 2
t°C
TE1
1 2
t°C
TE3
1 2
t°C
TE4
1 2
t°C
TE5
+
Y
U
-
3
2
5
1
SM2*
L
N
2
1
SM1*
L
N
PE
M3*
PE
U2
Z
U1
M1
Po
w
er input
230 V
AC
— ELECTRIC SHOCK HAZARD!
DI7
DI6
DO6
DO5
DO3
24V AC
~
230V AC
~
K1
190V AC
~
160V AC
~
Designation
Name
Type
Cable
M1
Supply fan
max 0.8 kW
M2*
Circulating pump
max 0.3 kW
3 х 0,75 mm
2
DD1*
Dry run protection relay
NC
2 х 0,75 mm
2
SM1*
Supply air damper actuator
LF230
2 х 0,75 mm
2
SM2*
Heat medium regulating valve actuator
LR 24 SR
3 х 0,75 mm
2
PK1*
Contact from fire alarm panel
NO
2 х 0,75 mm
2
P1
Remote mounted control panel
ALP
PD1
Pressure differential switch on the supply filter
NC
TE1
Outdoor temperature sensor
PT 1000 ST-01
TE3
Return heat medium temperature sensor
PT 1000 STw-02
TE4
Freeze protection sensor of the water heater
PT 1000 STw-02
TE5
Supply air temperature sensor
PT 1000 STa-02
1. The system is operable in case of no DD1 fluid pressure switch in the water heater. In this case the contacts 11 and 12 must be jumped.
2. The maximum connecting cable length from the P1 remote control panel is 10 m.
3. *— not included into delivery set, available as a specially ordered accessory.
4. ** maximum connecting cable length is 20 m.