11

air damper or any other compatible climatic equipment is sent.

Control signal parameters: 
•  maximum current 1A;
•  maximum voltage 250 V. 

Access to the control circuit board and connection of the external control equipment: 

•  unscrew the front part of the control panel;
•  remove the cover;
•  connect the external control unit to the control board;
•  assemble the control panel in the reverse order.

32  33  34 35 36

1.

2.

3.

External 

External 

External 

External 

control 

control 

control 

control 

unit

unit

unit

unit

SPEED CONTROL

1. Set the speed switch in 

STANDBY

 position. 

LED2

 glows. 

2. Enter the setup mode for exhaust and supply fan by pressing the 

MODE

 button quickly. 

Speed 

Times required to press 

MODE

 

button 

Indication of 

LED1

 and 

LED2

 during mode activation

LOW

4

four-time synchronous blinking 

MED

5

fi ve-time synchronous blinking 

HIGH

6

six-time synchronous blinking 

3. Adjust the fan speed using the 

EXHAUST

 and 

FRESH

 speed controllers.

4. Save the settings by pressing and holding 

MODE

 button, till the 

LED1

 and 

LED2

 indicators go out. 

To leave the speed setup mode without editing press shortly the 

MODE

 button. 

Example: adjust the 

MED

 speed. 

Содержание Frigate ERV 120 SR

Страница 1: ...USER MANUAL Heat energy recovery ventilation unit Frigate HRV 120 SR Frigate ERV 120 SR...

Страница 2: ...d in the box 5 Designation key 5 Technical data 6 Design and operation 7 Mounting and installation guidelines 8 Condensate Drainage 8 Connection to power supply 9 Unit Control System 10 Maintenance 14...

Страница 3: ...power supply prior to any installation operations The unit must be grounded Do not operate the unit outside the temperature range stated in theuser smanual Donotoperate theunitinaggressiveorexplosive...

Страница 4: ...mity to the unit OFF ON Disconnect the unit from power supply prior to any technical maintenance Do not allow children to operate the unit Avoid damaging the power cable Do not put any foreign objects...

Страница 5: ...E The unit is used for whole house mechanical ventilation of cottages offices hotels cafes conference halls and other residential and public premises INCLUDED IN THE BOX One ventilation unit One user...

Страница 6: ...ghtly differ from the model described here Frigate HRV 120 SR Frigate ERV 120 SR RPM min 1 2885 Noise level 9Ft 3 m Sones 2 Max transported air temperature F C 22 up to 140 30 up to 60 Housing materia...

Страница 7: ...IDELINES THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL POSSESSING REQUIRED TOOLS AND MATERIALS AFTER APPROPRIATE BRIEFING Be sure to provide sufficient service access w...

Страница 8: ...verflow The unit is designed for indoor installation and operation at the temperatures above 32 F 0 C If the expected ambient temperatures are below 32 F 0 C the drain system must be heat insulated an...

Страница 9: ...brown blue Y G PE M2 L M2 C M2 N 13 25 C2 24 C2 34 35 36 9 11 12 6 14 15 16 17 2 3 4 5 120 V 60 Hz PE Green 120V 12V 12V GND12V 24V L120VAC N 120VAC 12VAC 24VAC L N SW1 SW1 SW1 1 2 3 20 19 18 SW2 Low...

Страница 10: ...exceeds the set point the unit changes to the High Speed Mode 3 Humidistat The humidistat is used for indoor humidity control When indoor humidity increases above the set point the unit switches to th...

Страница 11: ...control unit unit unit unit SPEED CONTROL 1 Set the speed switch in STANDBY position LED2 glows 2 Enter the setup mode for exhaust and supply fan by pressing the MODE button quickly Speed Times requi...

Страница 12: ...Recirculation Recirculation Recirculation Recirculation No recirculation air exhaust only No recirculation air exhaust only No recirculation air exhaust only No recirculation air exhaust only ON OFF...

Страница 13: ...damage 4 Drain line maintenance once per year The drain line may get clogged by extracted particles Check the drain line functioning by filling the drain pan with water and clean the drain line if req...

Страница 14: ...grilles Air dampers air disc valves or louver shutters are closed Make sure the air dampers disc valves or the louver shutters are opened Noise vibration Dirty impeller Clean the fan impeller Loose s...

Страница 15: ...t improper maintenance or repair other than by VENTS US faulty installation or installation contrary to recommended installation instructions Labor to remove and replace products is not covered The du...