SURFACE MOUNTING

Fasten the fan to the surface using the screws with the dowels of appropriate size (not included in the delivery set). 
Make sure the fan is fastened securely.

Connect the air ducts of the appropriate diameter to the fan (connections must be airtight).
Air motion in the system must be in compliance with the direction of the arrow on the fan label.
To attain the best performance of the fan and to minimise turbulence-induced air pressure losses, it is recommended to connect the 
straight air duct section to the spigots on both sides of the unit while mounting.
Minimum recommended straight air duct section length is equal to 3 fan diameters (see the "Technical data" section).
If the air ducts are shorter than 1 m or not connected, the internal parts of the unit must be protected from ingress of foreign objects. 
To prevent uncontrollable access to the fans, the spigots may be covered with a protecting grille or other protecting device with 
mesh width not more than 12.5 mm.

3xD

3xD

ELECTRONICS OPERATION ALGORITHM

The EC motor is controlled by sending of an external control signal from 0 to 10 V to the X2 terminal block or by the R1 internal speed 
controller. Control method selection is carried out by means of the SW DIP switch:
  - DIP switch in IN position. The control signal is set by the R1 internal speed controller, which allows turning the fan on and off, smoothly 
regulating the fan motor rotation speed (air flow) in the range from minimum to maximum speed.
Rotations are controlled from the minimum (extreme left position) to the maximum (extreme right position).
When rotating clockwise, the rotations increase.
  - DIP switch in EXT position. The control signal is set by the S1 external control unit.

Содержание Boost 355

Страница 1: ...Boost 355 Boost 400 Inline mixed flow fan USER S MANUAL...

Страница 2: ...ertificate 13 Warranty card 13 This user s manual is a main operating document intended for technical maintenance and operating staff The manual contains information about purpose technical details op...

Страница 3: ...a hazardous or explosive environment containing spirits gasoline insecticides etc Do not close or block the intake or extract vents in order to ensure the efficient air flow Do not sit on the unit and...

Страница 4: ...rnal switching device such as a timer or connected to a circuit that is regularly switched on and off by the utility Precautions must be taken to avoid the back flow of gases into the room from the op...

Страница 5: ...res evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substances dust pathogeni...

Страница 6: ...Voltage V at 50 Hz 1 230 Power W 126 131 150 197 204 224 Current A 0 60 0 58 0 66 0 91 0 90 0 98 Maximum air flow m3 h 2090 2296 2485 2677 3136 3350 RPM min 1 1350 1400 1470 1320 1390 1446 Maximum tr...

Страница 7: ...izontal or vertical surface While installing the unit ensure convenient access for subsequent maintenance and repair Fasteners for fan mounting are not included in the delivery set and should be order...

Страница 8: ...cted the internal parts of the unit must be protected from ingress of foreign objects To prevent uncontrollable access to the fans the spigots may be covered with a protecting grille or other protecti...

Страница 9: ...ors cables wires The actual wire cross section selection must be based on the maximum load current maximum conductor temperature depending on the wire type insulation length and installation method Th...

Страница 10: ...ons Disconnect the air ducts from the fan Clean the fans with a soft brush cloth vacuum cleaner or compressed air Do not use water aggressive solvents or sharp objects as they may damage the impeller...

Страница 11: ...up after transportation at low temperatures allow the unit to warm up at operating temperature for at least 3 4 hours TROUBLESHOOTING Problem Possible reasons Troubleshooting The fan s do es not start...

Страница 12: ...Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual includin...

Страница 13: ...N CERTIFICATE The Boost_________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full...

Страница 14: ...14 Boost www ventilation system com...

Страница 15: ...15 www ventilation system com...

Страница 16: ...V208EN 04...

Отзывы: