STORAGE AND TRANSPORTATION REGULATIONS

•  Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range 

from +5 °C to + 40 °C and relative humidity up to 70 %.

•  Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing 

deformation.

•  Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
•  Follow the handling requirements applicable for the particular type of cargo.
•  The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and 

mechanical damage. The unit must be transported only in the working position.

•  Avoid sharp blows, scratches, or rough handling during loading and unloading.
•  Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at 

least 3-4 hours.

TROUBLESHOOTING

Problem

Possible reasons

Troubleshooting

The fan(s) do(es) not 
start.

No power supply.

Make sure the power supply line is connected correctly, 
otherwise troubleshoot the connection error.

Jammed motor.

Disconnect the fan from power supply. Troubleshoot 
the motor jamming. Restart the fan.

The fan has overheated.

Disconnect the fan from power supply. Eliminate the 
cause of overheating. Restart the fan.

Automatic circuit 
breaker tripping 
following the fan 
turning on.

High current consumption due to short circuit in 
power line.

Turn the fan off. Contact the Seller.

Noise, vibration.

The fan impeller is soiled.

Clean the impellers.

The fan or casing screw connection is loose.

Tighten the screw connection of the fan or the casing 
against stop.

The ventilation system components (air ducts, 
diffusers, louvre shutters, grilles) are clogged or 
damaged.

Clean or replace the ventilation system components 
(air ducts, diffusers, louvre shutters, grilles).

Содержание Boost 150

Страница 1: ...Boost 150 Boost 160 Boost 200 Boost 250 Inline mixed flow fan USER S MANUAL...

Страница 2: ...13 Installation certificate 13 Warranty card 13 This user s manual is a main operating document intended for technical maintenance and operating staff The manual contains information about purpose tec...

Страница 3: ...on the unit and do not put objects on it The information in this user s manual was correct at the time of the document s preparation The Company reserves the right to modify the technical characterist...

Страница 4: ...guard WARNING If there are any unusual oscillating movements immediately stop using the unit and contact the manufacturer its service agent or suitably qualified persons The replacement of parts of t...

Страница 5: ...favourable for the formation of hazardous substances toxic substances dust pathogenic germs Name Number Fan 1 pc User s manual 1 pc Packing box 1 pc Plastic screwdriver for the models with a timer 1 p...

Страница 6: ...ection rating against access to hazardous parts and water ingress is IP 4 The unit is rated as a class I electric appliance The unit design is constantly being improved thus some models may be slightl...

Страница 7: ...traight air duct section to the spigots on both sides of the unit while mounting Minimum recommended straight air duct section length is equal to 3 fan diameters see the Technical data section If the...

Страница 8: ...control voltage application to input terminal LT by an external switch e g indoor light switch After the control voltage is off the fan continues to operate within the set time period adjustable from...

Страница 9: ...a section The connection must be made using durable insulated and heat resistant conductors cables wires The actual wire cross section selection must be based on the maximum load current maximum condu...

Страница 10: ...arp objects as they may damage the impeller It is forbidden to remove or change the location of the balancers on the impeller as this can lead to increased level of vibration noise and reduce the serv...

Страница 11: ...up after transportation at low temperatures allow the unit to warm up at operating temperature for at least 3 4 hours TROUBLESHOOTING Problem Possible reasons Troubleshooting The fan s do es not start...

Страница 12: ...Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual includin...

Страница 13: ...TE The _____________________________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Techni...

Страница 14: ...14 Boost www ventilation system com...

Страница 15: ...15 www ventilation system com...

Страница 16: ...V208 1EN_A4_stkr 03...

Отзывы: