9

АОЕ

The unit operating area is shown below 

3-8 m

16 m

4-14 m

16 m

CONNECTION TO POWER MAINS

DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY ELECTRIC 

INSTALLATION OPERATIONS. CONNECT THE UNIT TO A CORRECT INSTALLED 

SOCKET WITH A GROUNDED TERMINAL. ANY INTERNAL CONNECTION 

MODIFICATIONS ARE NOT ALLOWED AND RESULT IN WARRANTY LOSS.

The unit must be operated only jointly with an automation system that enables the following functions: 
1. Disabling power supply to the heater when the fan is off. 
2. Air supply to the electric heating elements for heat removal within 2 minutes after the unit is off. 
3. Maintaining minimum air speed 2 m/s to avoid heating elements overheating. 
4. Power supply cut-off in case of overheating of the electric elements by means of the thermal switches mounted inside of the heater 

casing

5. Automatic heating capacity control to keep the maximum air temperature downstream of the electric 40 °C to avoid the 

heater overheating and reducing its service life.

The recommended suitable automation system for AOE 9, AOE 12, AOE 15 models is the control unit UET 15D and for the models 

AOE 18, AOE 24, AOE 30 is UET 30 D. The control unit UET and the matching mounting kit are available upon separate order. In this case 

replace the terminal box with a respective control unit and connect it to the internal terminal blocks of AOE unit in compliance with the 

wiring diagram stated in the UET user manual. 

The unit with a selected control system is rated for connection to three-phase ac 400 V / 50 Hz power mains. Connection to power 

mains of the unit with any control system must be performed with insulated, durable and heat-resistant conductors (cables, wires). 

The external power input 400 V / 50 Hz must be equipped with an automatic circuit breaker built into the stationary wiring to 

disconnect all the power mains phases. The circuit breaker QF position must ensure free access for quick power-off of the unit. The circuit 

breaker trip current must be in compliance with the current consumption of a specific AOE model. 

The recommended circuit breaker trip current and the cable cross sections for various AOE models are given un the table below. 

However, the conductor selection shall be based on the maximum permissible wire heating depending on the wire type, its insulation, 

length and installation method (i.e. overhead, in channels or inside the walls).

Содержание AOE 12

Страница 1: ...USER S MANUAL AOE series Air heating unit with electric heater...

Страница 2: ...technical parameters 5 Design and operating logic 6 Mounting and set up 7 Connection to power mains 9 Maintenance 12 Troubleshooting 12 Storage and transportation rules 12 Manufacturer s warranty 13...

Страница 3: ...erring the unit control the user s manual must be turned over to the receiving operator Symbol legend used in the manual UNIT MOUNTING SAFETY PRECAUTIONS WARNING DO NOT The unit must be disconnected f...

Страница 4: ...the unit from power supply prior to maintenance Do not let children operate the unit Do not damage the power cable while operating the unit Do not put any objects on the power cable Keep combustible g...

Страница 5: ...T IS NOT INTENDED TO BE USED BY CHILDREN PHYSICALLY OR MENTALLY DISABLED PERSONS PERSONS WITH SENSORY DISORDER PERSONS WITH NO APPROPRIATE QUALIFICATION ANY OPERATIONS WITH THE UNIT MUST BE PERFORMED...

Страница 6: ...material Painted steel Noise level 5 m dB A 55 61 Ingress protection rate IP 21 Weight kg 32 48 DESIGN AND OPERATING LOGIC The unit is designed for indoor air heating by means of the electric heater...

Страница 7: ...RSELY AFFECTS AERODYNAMIC AND HEATING CHARACTERISTICS AND THE UNIT SERVICE LIFE While mounting the unit provide the minimum required access to the unit for maintenance and repair The unit is designed...

Страница 8: ...ACKET MK AOW 25 AND MK AOW 40 WALL SURFACE MOUNTING CEILING MOUNTING min 300 mm The mounting bracket MKU available upon separate order is designed for wall or ceiling mounting and installation at the...

Страница 9: ...15D and for the models AOE 18 AOE 24 AOE 30 is UET 30 D The control unit UET and the matching mounting kit are available upon separate order In this case replace the terminal box with a respective con...

Страница 10: ...1 in the control circuit X3 Fan X2 Heater X2 Heater TERMINAL BLOCKS INSIDE OF THE TERMINAL BOX Terminal block X1 in the control circuit RT1 temperature sensor TK1 self resettable thermal switch normal...

Страница 11: ...tuated in case of unscheduled power outage or wrong selected control system The automatically resettable thermal switch with response temperature 50 C resets to operating condition after the heater co...

Страница 12: ...hanical shocks and strokes during handling operations Fault Possible reasons Fault handling The fan does not start up during the unit start up No power supply Make sure that the unit is properly conne...

Страница 13: ...details stated on the unit packing and in the user s manual User s failure to ensure timely technical maintenance of the unit External damage to the casing excluding external modifications of the uni...

Страница 14: ...requirements relating to electromagnetic compatibility was based on the following standards Quality Inspector s Stamp Air heating unit with electric heater has been connected to power mains pursuant...

Страница 15: ...15 Product type Air heating unit with electric heater Model Serial number Manufacturing date Sales date Warranty period Sales company Seller s seal WARRANTY CARD...

Страница 16: ...2013 V98EN 01...

Отзывы: