UNIT OVERALL DIMENSIONS [Inch]
W
W2
W1
W2
H1
L
Ø D
L1
A
H2+/*
H+/*
H +20*
H2 +20*
View A
Model
D
W
W1
W2
L
L1
H
H1
H2
DVUT(E) 300 HB EC
7 7/8"
24 7/16"
9 1/16"
7 11/16"
18 1/2"
20 1/2"
69 11/16"
58 1/8"
11 9/16"
*The unit height may be adjusted by means of leveling feet.
Model
DVUT 300 HB EC
DVUE 300 HB EC
Power supply voltage, 60 Hz [V]
1~120
Unit power consumption excl. electric heater [W]
132
Maximum unit current [A]
1,8
Maximum air flow [m3/h]
188
Noise level, 3 m [Sones]
1.9
Transported air temperature [˚F]
-13 ... +104
Casing material
painted steel
Insulation
1 9/16 inch mineral wool
Extract filter
G4 x 2
Supply filter
G4 + F8
Optional supply filter: material/size/filtration rate
H11+ F8
Connected duct diameter [inch]
7 7/8"
Weight [lbs]
304±3%
300±3%
Heat recovery efficiency [%]
78-92
73-89
Heat exchanger type
counter-flow
Heat exchanger material
polystyrene
enthalpy
SEC class
A
TECHNICAL DATA
The unit is designed for application with the ambient temperature ranging from +33.8 °F to +104 °F and relative humidity up to 80 %.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 35,6-37,4 °F
above the dew point temperature of the transported air.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
• IP22 for the unit connected to the air ducts
• IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.