TECHNICAL DATA
UNIT OVERALL DIMENSIONS [mm]
Units without water heater
A1
A2
A
B
B3
B4
B1
B2
Ø D
Model
A
A1
A2
B
B1
B2
B3
B4
D
AV02 CFH 1500-R(L)
AV02 CFH 2500-R(L)
1060
41 3/4"
838
33"
350
13 3/4"
1880
74"
789
31 1/16"
600
23 5/8"
325
12 13/16"
425
16 3/4"
18
11/16"
AV03 CFH 3500-R(L)
1390
54 3/4"
1003
39 1/2"
350
13 3/4"
2200
86 5/8"
890
35 1/16"
600
23 5/8"
357
14 1/16"
439
17 5/16"
AV07 CFH 5000-R(L)
AV07 CFH 6000-R(L)
1520
59 13/16"
1218
47 15/16"
500
19 11/16"
2500
98 7/16"
1430
56 5/16"
1000
39 3/8"
479
18 7/8"
690
27 3/16"
The full technical data list is stated in the supplied technical data sheet.
The unit is designed for indoor or sheltered use. The installation conditions must prevent ingress of atmospheric precipitations and direct
solar radiation at the ambient temperatures from -35 °C up to +50 °C. Outdoor unsheltered mounting is allowed provided an extra cover
and weather hoods are installed on the air ducts (not included in the delivery set).
The frost protection for the water drainage and connected pipelines must be provided during sub-zero ambient temperatures (if the unit
is equipped with an air cooler). The heat medium temperature in the water heat exchangers (if available) must be sufficient to prevent
their freezing. Hazardous parts access and water ingress protection rating:
• IP54 for the unit motors
• IP42 for the assembled unit connected to the air ducts without extra cover or weather hoods
• IP44 for the assembled unit with connected air ducts, extra cover and weather hoods (specially ordered accessories)
• IP00 for the unit not connected to the air ducts
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.