23
3.5 „COMMUNICATION SETTINGS“:
3.5.1 „AHU BMS SETTINGS “
- AHU RS485 interface settings:
•
ADDRESS 1
*
•
BAUDRATE 19,2kbps
*
,
•
PARITY NONE
*
,
•
STOP BITS 1
*
,
3.5.2 „REMOTE MB SETTINGS “
- control panel RS485 interface settings:
•
BAUDRATE 19,2kbps,
•
PARITY NONE.
•
STOP BITS 1
It is possible to find AHU controller by its Modbus address.
3.6 „
REMOTE CONTROLLER DEFAULT PARAMETERS“
– restore remote controller default parameters (it
is necessary to confirm action) and launches guide to set language, date, time, preferred temperature (preset
is 21
°
C
*
). Work schedule will be automatically filled in according to AHU location place and selected work
hours.
4. WORK SCHEDULE
Events are set hourly (0h – 23h) for all week. Every hour is assigned with preset containing preferred
temperature and fan speed (see 2.1). Every preset has its own icon
. If temporary event is selected in the initial
window work schedule is not active.
Work schedule has 2 modes:
•
it is possible to view settings for the week while selecting a weekday,
•
to edit press
. Select weekdays taping and swiping icons. Select hours you want to edit
taping
and swiping icons. Select preset for your selection. Press
to save.
Note: * - default settings.
5. CONTENTS
•
Remote control „3S 1.0“
1 piece.
•
Battery, 1220 type
1 piece.
•
Communication cable
1 piece.
•
Box1 piece
1 piece.
•
User manual
1 piece.