Technical Specification
Sentinel Kinetic MVHR Installation & Commissioning
7
Sentinel Kinetic Summer By Pass Models.
The Sentinel Kinetic B, BH, Plus B are fitted with a Summer By Pass (SBP) and will provide energy-free heating
and energy-free cooling when the house temperature and ambient temperature allows.
If the room is warmer than the set (shown as "indoor") temperature (i.e. you need the room to be cooler) and the
outdoor air is cooler than the actual room temperature (i.e. the outdoor air could cool your room) then the SBP will
open and the unit will supply cooler air to your room.
If the room is cooler than the set ("indoor") temperature (i.e. you need the room heating) and the outdoor air is
warmer than the actual room temperature (i.e the outdoor air could heat your room) then the SBP will open and
the unit will supply warmer air to your room.
Note that the above only applies whilst the outdoor air temperature is above 14 C (adjustable) in order to prevent
cold draughts.
The set ("indoor") temperature should be set 2 or 3 degrees higher than the central heating thermostat and 2 or 3
degrees below any air conditioning thermostat if fitted. This will prevent any clash between the separate systems.