Vent-Axia Lo-Carbon Silhouette Series Скачать руководство пользователя страница 4

 

 

 

 

 

B. WIRING.

 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE 
ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION / OR 
MAINTENANCE. 
 

IMPORTANT 

 

The

 

Controller

 

MUST

 be surface mounted to allow air to freely circulate around the 

unit. When installed in a loft void it 

MUST

 

NOT

 be enclosed or covered with insulation. 

  The fan should only be used in conjunction with fixed wiring.  

  The cross - sectional area of supply cord used should be ranged from 1 -1.5mm

2

  Cable entry can only be made from the rear of the fan.  

 
 

1.  Select and follow the appropriate wiring diagram (Fig. 2 & 3). 
2.  Check all connections have been made correctly and ensure all terminal connections and 

cable clamps are securely fastened. 

3.  Ensure the impeller rotates and is free from obstructions. 
 

C. SETUP 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED 
FROM THE POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE. 

 

ACCESSING THE CONTROL SETTINGS – (Fig. 4) 

1. 

Loosen the screw in the bottom of the grille and remove the front grille. 

2. 

Carefully pull the inner cap from the centre of the fan away from the chassis.  

3. 

Adjust the settings as outlined below.  

 

SPEED SETTING: 

BEFORE SETTING THE SPEED, SWITCH OFF THE MAINS SUPPLY. SPEED SHOULD ONLY BE 
SET BEFORE OR DURING INSTALLATION. 

The fan has two speed settings for different installation requirements: 
 

1) High 

speed: 

 

  100SVT and 100SVH models: Dip switch 2 in 

the ‘OFF’ position. (

Fig.5 – and right)

 

  100SVB model: Remove jumper. (

Fig.5)

 

 
 
2) 

Low speed (Factory set):  

  100SVT and 100SVH models: Dip switch 2 

should be in the ‘ON’ position. (

Fig.5 – and right)

  

  100SVB model: Replace jumper. (

Fig.5)

  

 
Dip switch 1 should be in the ‘OFF’ position (100SVT and 100SVH models 
only).  
 
 

1  2

ON

High speed (T & H) 

1  2

ON

Low speed (T & H) 

Содержание Lo-Carbon Silhouette Series

Страница 1: ...B 441512A 100SVT 441513A 100SVH PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Silhouette Lo Carbon SELV RANGE FAN UNITS 12V DC SELV CLASS III CONTROLLER 220...

Страница 2: ...f time H Where ducted Fans are used to handle moisture laden air a condensation trap should be fitted Horizontal ducts should be arranged to slope slightly downwards away from the Fan I This appliance...

Страница 3: ...n be used with short lengths of rigid ducting but check details first with your Vent Axia sales centre Where an excessive amount of moisture is present in the air a condensation trap will need to be i...

Страница 4: ...tions C SETUP WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION OR MAINTENANCE ACCESSING THE CONTROL SETTINGS Fig 4 1 Loosen the screw in t...

Страница 5: ...arbon Silhouette 100SVT 100SVH Fig 1 Siting the fan N L 1 Phase Supply 220 240V 50Hz FUSE Switched Fused Spur 3A LS 12V 0V Controller Fan 12V D C SELV Supply N L LS LS N L 2 1 3 N LS 12V 0V Controller...

Страница 6: ...to turn the adjuster Fig 5 ANTI CLOCKWISE 4 Replace the fan grille HUMIDITY SET POINT ADJUSTMENT 100SVH MODEL ONLY BEFORE ADJUSTING THE CONTROLLER SWITCH OFF THE MAINS SUPPLY HUMIDISTAT SHOULD ONLY B...

Страница 7: ...ER SUPPLY DURING MAINTENANCE 1 At intervals appropriate to the installation the fan should be inspected and cleaned to ensure there is no build up of dirt or other deposits 2 Wipe the inlets and front...

Страница 8: ...tion replaced without charge provided that the product Has been installed and used in accordance with the instructions given with each unit Has not been connected to an unsuitable electricity supply T...

Отзывы: