Vent-Axia Lo-Carbon Minivent Series Скачать руководство пользователя страница 3

 

3

~

N

L

1 Phase Supply

(220-240V 50Hz).

FUSE

Switched 

Fused Spur

+

L

N

8V 11V

-ve

Controller

-

Fan

SELV Supply

Pullcord

Lower Speed 

for Toilet

Higher Speed for 

Bathroom 

Bath/Utility Room

L

s

~ N

Switch

Toilet

SELV Supply

N L

+ve -ve

+

-

Fan

Select Bath/Utillity (High Speed) 

or Toilet (Low Speed) using the 

selector switch

mins

Timer Adjuster.

Control Timer

B. 

WIRING.

 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM 
THE POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE. 

 

NOTE: The

 

Controller

 

MUST

 be surface mounted to allow air to freely circulate around the unit. When 

installed in a loft void it 

MUST

 

NOT

 be enclosed or covered with insulation. 

 

1.  Select and follow the appropriate wiring diagram (Fig. 2-3). 
2.  Check all connections have been made correctly and ensure all terminal connections and cable clamps are 

securely fastened. 

3.  The cable entry must be made using the cable grommet. 
4.  Ensure the impeller rotates and is free from obstructions. 
 

Fig. 2. 

Minivent Lo-Carbon B 
Basic Model. 

 

Select the wiring configuration required for the Toilet or Bathroom. 
 
 
 
 
 
 
 
 
 
 
 

Fig. 3. 

Minivent Lo-carbon T 
Timer Model. 

 

Switch the selector switch to the required mode. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Timer Adjustment. 
 

The overrun time period is factory set to 15 minutes. The overrun time period may be adjusted from 5-25 minutes, 
by altering the adjuster on the back of the Control Timer. 

 

Before adjusting the timer, switch off the Mains Supply. 

 

1.  Remove the Controller Unit. 
2.  To REDUCE the operating time, turn the adjuster ANTI-CLOCKWISE on the back of the Controller. 
3.  To INCREASE the operating time, turn the adjuster CLOCKWISE on the back of the Controller. 
4.  Replace the front of the Control Timer. 
5.  Reconnect the mains supply. 
 
 