Vent-Axia HR300RW6 Скачать руководство пользователя страница 5

2.0 Site Requirement

5

2.1

Information

1. The unit is designed for installation in external

walls with a thickness of between 150mm to

315mm.

2. The unit must be sited and connected by a

suitably qualified person and be in accordance

with current UK Building Regulations and I.E.E.

Wiring Regulations (BS 7671).

3. The unit is intended for permanent connection

to the mains electrical supply.

4. The unit is intended for fixed wiring installation.

5. Wiring to the unit in the UK must be via a

switched fused spur. The switched fused spur

must have a 3mm minimum contact gap in all

poles.

6. Ensure that the mains electrical supply is

compatible with the rating label attached to the

product.

7. The unit must be sited such that the ambient

temperature will not exceed 40° C.

8. Do not site the appliance in the vicinity of

excessive levels of airborne oil or grease.

9. If the unit is installed in a room containing a

fuel burning appliance, the installer must ensure

that air replacement is adequate for both

appliances.

10. The unit must not be installed at a level below

500mm from the floor.

11. The internal grille surround must be sited at

least 125mm away from any wall or projecting

surface (Fig. 3).

12. The external grille of the unit must be sited at

least 

6

00mm away from any flue of gas or solid

fuel appliances. This is to avoid back flow of

gases entering the room.

13. All safety regulations and requirements must

be strictly followed to prevent hazards to life and

property both during and after installation and

during subsequent maintenance or servicing.

14. Ensure the mains electrical supply is switched

off before commencing installation or

maintenance.

Fig. 3

125mm

Min

125mm

Min

500mm 

Min Above

Floor Level

Содержание HR300RW6

Страница 1: ...HR300RW6 Semi Remote Wall Mounted Heat Recovery Ventilator Installation and Servicing Instructions Please leave these instructions with the user...

Страница 2: ...2...

Страница 3: ...3 1 0 Introduction 4 2 0 Site Requirements 5 3 0 Installation 6 4 0 Electrical 8 5 0 Maintenance 9 Section Page Contents...

Страница 4: ...esh intake airflow This provides up to 70 heat recovery from the stale extracted air 1 2 Ancillary Equipment 1 The HR300RW6 unit can be used in conjunction with a range of ancillary equipment Controll...

Страница 5: ...xceed 40 C 8 Do not site the appliance in the vicinity of excessive levels of airborne oil or grease 9 If the unit is installed in a room containing a fuel burning appliance the installer must ensure...

Страница 6: ...controllers and work out the cable runs WARNING Before deciding on the final position for the unit check there are no buried cables pipes or obstructions on the outside wall Cable requirements Suitabl...

Страница 7: ...lace with the two fixing screws provided NOTE Ensure the fixings DO NOT inhibit removal or replacement of the heat exchanger 5 Make good around the case 6 Fit the bezel on the inside to cover the maki...

Страница 8: ...cket and connect incoming wires to the appropriate terminals Figs 7 8 4 Replace plug into socket 5 Slide the heat exchanger into the unit Fig 9 6 Locate the connection spigot plate on to the front of...

Страница 9: ...connection spigot plate Fig 10 4 Slide out the heat exchanger Fig 10 The heat exchanger should be washed in warm soapy water and dry thoroughly 5 Reassemble in reverse order ensuring the heat exchang...

Страница 10: ...6 0 Notes 10...

Страница 11: ...11...

Страница 12: ...Vent Axia Ltd Fleming Way Crawley West Sussex RH10 9YX www vent axia com Comp No 372561 Iss B 0405...

Отзывы: