Vent-Axia HR100S Скачать руководство пользователя страница 4

PRODUCT DESCRIPTION 

The HR100S is a surface mounting heat recovery ventilation unit for use in bathrooms and toilets.  It 
is designed for mounting on an external wall having a thickness from 100 to 400mm. 

The units twin impeller and heat recovery arrangement simultaneously supplies and extracts air 
while transferring heat from the stale exhaust airflow to the fresh intake airflow.  This providesup to 
60% heat recovery from the stale air. 

Separation of the exhaust airflow and the intake airflow is maintained through the unit and the 
special duct supplied with it. 

The unit incorporates electrical connections for operating at two speeds, thereby providing trickle 
and/or boost ventilation options (see Fig.5). 

The overall electrical power consumption of the unit is 35 watts at high speed and 15 watts at low 
speed.  The units motor is fitted with standard thermal overload protection protection,  which in the 
event of a fault causing the motor to overheat will cut of the electrical supply to the motor. 

The fan unit may be connected through a vent-axia ecotronic humidistat (Stock Ref. 563532) or 
Ambient Response Humidistat (Stock Ref.563550), which automatically switch the fan unit from 
trickle to boost ventilation when the relative humidity in the room exceeds a pre-set adjustable level. 

CABLE RUNS 

Decide where to site the ventilation unit and work out the cable runs.  When using surface wiring 
which is not contained in conduit, the wiring must be securely anchored to the mounting surface. 

Install the cable runs in conjunction with a fused and switched connection unit located in the vicinity 
of where the ventilation unit will be sited.  Ensure that the cables for the ventilation unit extend at 
least 400mm from the mounting surface. 

FITTING INSTRUCTIONS (SEE FIG.4) 

1. Remove the duct, grille assembly and heat recovery ventilation unit from the packaging. 

2.  After noting the positions of the duct spigot and optional cable entry grommets on the top and 
rear of the housing  (see  Fig. 1). cut  a 114mm  diameter  hole through the wall. 

3. Cut the duct to a length which will provide for a flush finish with the internal and external wall 
faces.    DO NOT CUT THE END OF THE DUCT WHICH IS SLOTTED TO ACCEPT THE 
EXTERNAL GRILLE SPIGOT. 

4. With the web in the duct vertical, the slotted end of the duct  to  the  outside  and  the  duct  
sloping  slightly downwards to the outside for drainage of condensation, fix the duct in the wall by 
applying suitable gap filler between the duct and hole.  The filler must create a flush finish at the 
outer wall face to allow the external grille to be fixed satisfactorily. At the inner wall face the filler 
must be recessed at least 20mm to allow the duct spigot, on the back of the housing, to locate over 
the duct (see Fig.2). 

5. Remove the cover from the unit after removing the two retaining screws in the side and 
slackening the two retaining screws in the bottom of the cover. 

Содержание HR100S

Страница 1: ...HR100S Heat Recovery Ventilation Unit Surface mounting two speed heat recovery extract and intake unit for bathrooms and toilets Installation and Maintenance Instructions Stock Ref No HR100S 141 10 010 ...

Страница 2: ...ected and tested by a suitably qualified person after completion 3 Ensure the mains supply voltage frequency and phase complies with the rating label 4 The unit should be provided with a local double pole fused spur fitted with a 3A fuse having a contact separation of at least 3mm 5 These units must be earthed 6 Precautions must be taken to avoid the back flow of gases into the building from the o...

Страница 3: ...pply will energise both motor windings and cause the motor to overheat and cutout INSTALLATION GUIDANCE 1 The installer is responsible for the installation and electrical connection of the system on site It is the responsibility of the installer to ensure that the equipment is safely and securely installed and left only when mechanically and electrically safe 2 All regulations and requirements mus...

Страница 4: ... work out the cable runs When using surface wiring which is not contained in conduit the wiring must be securely anchored to the mounting surface Install the cable runs in conjunction with a fused and switched connection unit located in the vicinity of where the ventilation unit will be sited Ensure that the cables for the ventilation unit extend at least 400mm from the mounting surface FITTING IN...

Страница 5: ... 2 Remove the terminal block cover after unscrewing the retaining screw 3 Remove the minimum amount of sheath and insulation from the supply cable and leads Slacken the cable clamps and feed the cable through the clamps Connect the conductors coloured red live L black neutral N and green yellow earth E to the appropriate terminals marked L1 L2 N and E of the terminal block in accordance with the w...

Страница 6: ...he housing by grasping and gently but firmly pulling on its central vertical member 5 Wash the cover filter and heat exchanger in warm water using a mild detergent and subsequently dry them thoroughly Keep water away from all electrical components and wiring within the appliance 6 Replace the heat exchanger 7 Replace the filter in the cover 8 Refit the cover and tighten the four retaining screws 9...

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ...3 h 0 56 Control Factor Control Typology CTRL Typology Control Factor CTRL 1 00 Control Typology Manual Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs TBC Mixing Rate of Non Ducted BVUs not intended to be equipped with one duct connection on either supply or extract air side TBC Filter Warning RVU ...

Страница 12: ...rating label attached to the unit Has not been subjected to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product carriage paid to your original supplier or nearest Vent Axia Centre by post or personal visit Please ensure that it is adequately packed and accompanied by a letter ...

Отзывы: