Vent-Axia Centrif Duo DP 25 63 20C Скачать руководство пользователя страница 4

SURFACE MOUNTING

 

(PANEL/CEILING)

 

1. 

Remove the Front Cover Assembly by slackening the two screws by two turns (

fig.2.) 

 Lift the 

front assembly away from the bottom edge first, then the top edge

.

  

2. Cut 

105mm hole, then suitable screw holes in the panel, ensuring that there is sufficient 

space for the product to be installed and that the filter (sold separately for the Centrif Duo 
Plus) can be removed for maintenance. Either the cardboard fitment or the fan chassis can 
be used as a template. The Spigot can be removed temporarily to make it easier. (

Fig 1 & 3

). 

3. 

Set-up the appropriate speed selection and other features as outlined in 

Section B SETUP. 

 

4. 

Remove the small Terminal Block Cover in the top right corner (

fig 3

). 

5. 

Attach the ducting to the Spigot and locate the fan into the hole in the panel. Feed the wiring 
through the hole in the Chassis next to the Terminal Block as you do so. 

(fig. 4)

 

6. 

Secure into position using appropriate fixtures. 

7. 

Select and follow the appropriate wiring diagram in 

Section C WIRING.

 

8. 

Replace the little Terminal Block Cover over the Terminal Block (

fig.4

). 

9. 

Ensure the Impeller rotates freely (

fig.3

). 

10.  Replace the Front Cover Assembly and tighten the two screws (

fig.2.)

11.  Make sure that all covers are on correctly to ensure the optimum performance and water 

ingress protection of the fan. 

12.  Switch the mains power supply on and check the fan is operating correctly. 
 

SURFACE MOUNTING

 

(WALL)

 

For through-the-wall installations, a Wall Kit (25 41 02 White / 25 41 00 Brown) can be used. 
1. 

Remove the Front Cover Assembly by slackening the two screws by two turns (

fig.2.) 

 Lift the 

Front Cover Assembly away from the bottom edge first, then the top edge. 

2. Cut 

115mm hole through the wall, ensuring that there is sufficient space for the product to 

be installed and that the Filter (

fig.3

) can be removed for maintenance.  

3. 

Insert the wall sleeve with the larger diameter sleeve on the room-side and cement the ends 
into position flush with the wall faces. The wall sleeve should be angled downwards, away 
from the fan, to allow any condensation to drain to the outside. 

4. 

Outside Grille: Using the Grille’s back plate as a template, mark the fixing hole centres on the 
wall. Drill and plug the wall and fix the Grille into position. Ensure the louvres are pointing 
downwards. 

5. 

Set-up the appropriate speed selection and other features as outlined in 

Section B SETUP.

 

6. 

Remove the little Terminal Block Cover in the top right corner (

fig 3

). 

7. 

Using the fan chassis as a template, carefully sliding the Spigot into the Wall Liner, mark the 
fixing hole centres on the wall. Alternatively, the cardboard fitment can be used as a 
template. 

8. 

Drill and plug the wall using the fixings provided. 

9. 

Feed the wiring through the hole near the Terminal Block and secure the fan into position 
using the screws provided.  

10.  Select and follow the appropriate wiring diagram in 

Section C WIRING.

 

11.  Replace the Terminal Block Cover (

fig.4

).  

12.  Ensure the Impeller (

fig.3

) rotates freely. 

13.  Replace the Front Cover Assembly and tighten the two screws (

fig.2

).  

14.  Make sure that all covers are on correctly to ensure the optimum performance and water 

ingress protection of the fan. 

15.  Switch the mains power supply on and check the fan is operating correctly. 
 

FLUSH MOUNTING (PANEL/CEILING)  

A Flush Mount Kit (439256) is required. 
1. 

Remove the Front Cover Assembly by slackening two screws by two turns (

fig.2).

 Lift the 

front assembly slowly from the bottom edge first, then the top edge.  

2. 

Mark and cut a rectangular hole 222mm (w) x 253mm (h) through the panel ensuring that 
there is sufficient space for the product to be installed and that the Filter (

fig.3

) can be 

Содержание Centrif Duo DP 25 63 20C

Страница 1: ...ef N Centrif Duo P 25 61 20C Centrif Duo T 25 62 20C Centrif Duo DP 25 63 20C Centrif Duo HTP 25 64 20C Centrif Duo Plus P 43 16 13A Centrif Duo Plus T 43 16 14A Centrif Duo Plus DP 43 16 15A Centrif Duo Plus HTP 43 16 16A Centrif Duo Centrif Duo Plus Installation and Wiring Instructions Centrif Duo Plus Centrif Duo ...

Страница 2: ...y Washable filter available separately for Centrif Duo Plus Pullcord Trickle speed LS connection to boost from a remote switch from off T DP HTP or trickle speed DP HTP only Two boost speed options available selectable during installation Adjustable timer overrun 1 30 mins approx Adjustable humidity sensor default 60 RH approx ...

Страница 3: ... be used where it is liable to be subject to direct water spray for prolonged periods of time I Where ducted fans are used to handle moisture laden air a condensation trap should be fitted Horizontal ducts should be arranged to slope slightly downwards away from the fan J This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or la...

Страница 4: ...hat there is sufficient space for the product to be installed and that the Filter fig 3 can be removed for maintenance 3 Insert the wall sleeve with the larger diameter sleeve on the room side and cement the ends into position flush with the wall faces The wall sleeve should be angled downwards away from the fan to allow any condensation to drain to the outside 4 Outside Grille Using the Grille s ...

Страница 5: ...STALLATION OR MAINTENANCE 1 OPERATION i As standard the HTP models will run continuously at trickle speed until either the pullcord LS or humidistat call for boost speed To disable the constant trickle option remove the cover over the PCB to the right of the impeller and remove the link wire between terminals 4 and 5 on the PCB fig 7 ii The pullcord on the DP models will cycle between off trickle ...

Страница 6: ...ty adjuster fig 4 7 CLOCKWISE This makes the fan less sensitive to RH i e the fan will come on at a higher RH The fan will continue to run at boost after the RH has dropped below the set point for the time period set by the timer adjustment see 3 TIMER ADJUSTMENT above C WIRING WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING INSTALLATION OR MAINTENANCE...

Страница 7: ... lubrication Fig 1 Backdraught shutter assembly Flaps vertical Spigot Fig 2 Centrif Duo Plus Centrif Duo Cover Assembly Cover Screws Retaining edge for optional filter Centrif Duo Plus only Insert flat bladed screwdriver in here and pull Filter out to remove it ...

Страница 8: ...f Duo models have a metal mesh filter clipped on to the rear of the cover It can be removed easily and washed too Fig 4 Terminal Block Cover Cable Clamp Terminal Block Timer Adjustment T and HTP models only Turn clockwise to increase overrun timer length Humidity Adjustment HTP models only Turn clockwise to raise set point decrease sensitivity ...

Страница 9: ...9 Fig 5 Frame from optional Flush Mount Kit 4 screws Back Box Fig 6 Panel Clip Screw 4 off Panel Clip 4 off Chassis ...

Страница 10: ...10 Terminals Å1 Å2 Å3 Å4 Å5 See page 5 Section B Set Up Timer adjustment Humidity adjustment Fig 7 Setup HTP model shown PCBs may vary in look ...

Страница 11: ...11 Fig 8 Siting of the fan 3 2 ...

Страница 12: ... Axia Ltd Fleming Way Crawley RH10 9YX abc Head Office Fleming Way Crawley West Sussex RH10 9YX Tel 01293 526062 Fax 01293 551188 UK NATIONAL CALL CENTRE Newton Road Crawley West Sussex RH10 9JA SALES ENQUIRIES Tel 0844 8560590 Fax 01293 565169 TECHNICAL SUPPORT Tel 0844 8560594 Fax 01293 532814 441678 F 0909 N L Ls 1 Phase Supply 220 240V 50 Hz 3A Fuse Pull Cord Lamp 3 Pole Isolator Switch Ceilin...

Отзывы: