INSTALLATION AND WIRING INSTRUCTIONS FOR ACQ ACOUSTIC FAN

IMPORTANT – READ THESE INSTRUCTIONS FULLY BEFORE COMMENCING THE INSTALLATION

DO NOT install this product in areas where the following may be present or occur: -

•

Excessive oil or a grease laden atmosphere.

•

Corrosive or flammable gases, liquids or vapours.

•

Ambient temperatures higher than 50°C or less than –15°C.

•

Relative humidity above 95%.

•

Possible obstructions which would hinder the access or removal of the fan.

•

Sudden ductwork bends or transformations close to the fan.

SAFETY GUIDANCE NOTES

A. All wiring must be in accordance with current I.E.E. Regulations, or the appropriate standards of your country. The

equipment should be provided with a local double pole isolator switch having a contact separation of at least 3mm.

B. Ensure that the mains supply (Voltage, Frequency and Phase) complies with the rating label.
C. The fan should only be used in conjunction with the appropriate Vent-Axia products.
D. It is recommended that the connection to the terminal box is made in flexible cable or conduit for easy maintenance.
E. The fan should not be sited within 600mm of/or 2250mm above a bath/shower tray, in accordance with the current

I.E.E Regulations for bathrooms.

F. When the fan is used to remove air from a room containing a fuel-burning appliance, ensure that air replacement is

adequate for both the fan and the fuel-burning appliance.

G. Where a fan is used to supply air into a room, ensure that the fan intake is located a minimum of 600mm from any

flue outlet.

H. This fan is designed as an inline duct fan to  be positioned between lengths of ducting. Short duct runs terminating

within 1.5m must incorporate suitable guards unless the fan is mounted higher than 2.3m.

I. This fan should not be used where it is liable to be subject to direct water spray from hoses etc.
J. Where ducted fans are used to handle moisture-laden air, a condensation trap should be fitted. Horizontal ducts

should be arranged to slope slightly downwards away from the fan.

K. Certain applications may require the installation of sound attenuation material to achieve the sound levels required.

 An auto transformer speed controller is also recommended.

INSTALLATION

FAN MOUNTING

1. The fan is suitable for mounting at any angle.
2. Securely mount the fan using the appropriate holes in the flanges, drop rods, bolts, anti-vibration mounts etc.
3. Flexible connectors should be used at the fan inlet and outlet.
4. Ensure that there is an adequate clearance for accessing the fan and the removal of the access panel if appropriate.

WIRING

WARNING: - THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY

DURING INSTALLATION AND / OR MAINTENANCE. THE EQUIPMENT MUST BE EARTHED.

1. Select and follow the appropriate wiring diagram (

Figs.1-6)

2. Check that all connections have been made correctly. Ensure that all terminal screws and cable clamps are securely

fastened.

3. The cable entry must be by a suitable grommet or cable gland.
4. Switch the mains supply on and check the system is operating correctly.

Содержание ACQ 100-12C

Страница 1: ...LEASE LEAVE THESE INSTRUCTIONS WITH END USER Installation Set up and Operating Instructions Stock Ref No ACQ 100 12C ACQ 200 12C ACQ 400 14C ACQ 125 12C ACQ 250 12C ACQ 500 14C ACQ 150 12C ACQ 315 12L...

Страница 2: ...supply air into a room ensure that the fan intake is located a minimum of 600mm from any flue outlet H This fan is designed as an inline duct fan to be positioned between lengths of ducting Short duc...

Страница 3: ...rication OVERHEATING PROTECTION The fan motor is fitted with Standard Thermal Overload Protection This will automatically switch the fan Off in the event of a fault condition If this occurs isolate th...

Страница 4: ...ROLLER ACQ 100 12C ACQ 200 12C ACQ 125 12C ACQ 250 12C ACQ 150 12C ACQ 315 12LC ACQ 160 12C ACQ 315 14HC 2 5A ELECTRONIC SPEED CONTROLLER W103 03 102M ACQ 100 12C ACQ 250 12C ACQ 125 12C ACQ 315 12LC...

Страница 5: ...LOAD RELAY MUST BE FITTEDTOPROVIDEMOTOR PROTECTION THREE PHASE FAN CONTROLLED BY D O L STARTER N B LINKSBETWEEN TERMINALS 3 TOA1 AND 5 TO 95 MUST BE FITTED ANDTHELINKBETWEEN TERMINALS 24AND 96 MUST BE...

Страница 6: ...6 Fig 6 THREE PHASE FAN CONTROLLED BY 5 STEPAUTO TRANSFORMER 3 PHASEAUTO TRANSFORMERSPEED CONTROLLER 103 14 304 ACQ 500 34C...

Страница 7: ...7 DIMENSIONS mm...

Страница 8: ...thorised by the company IFCLAIMINGUNDERTERMSOFGUARANTEE Please return the complete product carriage paid to your original supplier or nearest Vent Axia Centre by post or personal visit Please ensure t...

Отзывы: