29
Humidity Output Polarity*
(Setup Step 60)
Open (Normally Open)
means no voltage is sent to the
HUM
output when there is no
demand for humidity.
Closed (Normally Closed)
means voltage is sent to the
HUM
output when there is no
demand for humidity.
Dehumidify Output Polarity*
(Setup Step 61)
Open (Normally Open)
means no voltage is sent to the
DEHUM
output when there is no
demand to dehumidify.
Closed (Normally Closed)
means voltage is sent to the
DEHUM
output when there is
no demand to dehumidify.
Dehumidify Only With Cooling
(Setup Step 62)
When set to ON, Dehumidify will only turn on with a 1st stage cooling demand.
When set to OFF, Dehumidify will turn on at any time that the room humidity exceeds
the dehumidification setpoint.
Press the SETUP button, then press MODE repeatedly until the
desired setup step appears. Use the WARMER or COOLER buttons
to make selection. Press MODE to advance to the next step.
Press/hold MODE to go backwards to prior steps. Press SETUP to
leave the setup screens.
WARMER
COOLER
MODE
SETUP
Setup Steps
Light Activation Sensitivity
(Setup Step 63)
With the lights on in the space, press the FAN button to set the sensitivity of the light sensor. This
light level will be the minimum light level needed to bring in occupied setpoints. When adjusting the
sensitivity, the prior setting (0-199) will show in the clock display and the current light level (0-199)
will show as the cool setpoint. Press FAN to store the present light level and press MODE to move
to the next step.
Note: The Skyport web app can track “lights on” runtime. This is accomplished by accumulating the
hours that the light sensor of the thermostat recognizes that the lights are on.
To use this feature of Skyport, adjust the light activation sensitivity.
Step 64 below does not need to be On for Skyport to accumulate “lights on” runtime.
Light Activation to Occupied
(Setup Step 64)
This feature allows the thermostat to go from Occupied settings to Unoccupied settings when the
room lights are turned off and the program is unoccupied. It also allows the thermostat to return to
the Occupied 1 settings once the lights come back on.
OFF
= Light Activation not used.
ON
= Light
Activation is used.