background image

MA-AL-T73E-01-03 Manual TUL373EN eng rev3 

 

   Rev.3 Page 3 of 4 

 
 

 
Connection of control board (placed behind the front panel)  

Refer to picture 3 

 

Relay “mains missing” – Terminals 10 – 11 – 12 (operating with SELV tensions) 
 
Relay output with intervention for missing mains and programmable activation delay 
 
Jumper on JP1 to have a delay of 15 seconds 

 

jumper on J3 to have a delay of 120 minutes 

Jumper on J1 to have a delay of 15 minutes 

 

jumper on J4 to have a delay of 240 minutes 

Jumper on J2 to have a delay of 60 minutes 
 

In order for the power supply to be in conformity to the certification , the jumper must be set on JP1 or J1, as the norm talks 
about a max delay of 30 MINUTES of missing mains. On the contrary, the conformity decades.  
 
Note: if no jumper is inserted, the “mains missing” relay will never activate. 
 

Relay of “failure indication” – Terminals 4 – 5 – 6 (operating with SELV tensions)  
 
Relay  output for failure indication, it is active for: 
Low battery (tension lower than 22 Vdc) 
Overcharged battery (tension over 28,5 Vdc) 
Resistance battery > 1 ohm 
 

Start of the system: 

 even if not imperative, the following sequence of connection is suggested: 

1. 

Connect mains and ground to the concerned terminal  J1. The charge Led flashes and after about 30 seconds the missing 

battery Led flashes 

2. 

Connect the battery. After 20 seconds the Led switches off 

3. 

Connect the charges: the Leds indicating the current supplied light up 

 
SERVICING 
 

Periodical  programmed servicing must be carried out by qualified personnel in order to prevent the possibility of a malfunctioning of the 
power supply. It is recommended to carry out servicing every 6 months and to evaluate control panel of the system in order to check 
possible alarms during tests. 
 
Check the connections of the 230 Vac supplying lines 
Check the connections of the alarm indication lines and related shields 
Check the battery connections, they have to be well tightened and there must be no oxidation 
Check the output tension on the charge (see electrical specifications) 
 
Although the power supply is equipped with a self-diagnosis system carrying out a periodical control of the battery and indicating 
possible failures, it is suggested to manually check the battery every six months. 
 
Disconnect the battery and check if the tension of the power supply is within the values shown. 
After re-connecting the battery, disconnect the primary supplying and check if the battery can maintain the tension on the higher 23 Vdc 
charge. On the contrary, replace battery immediately. 
Check presence of related alarms during tests. 

 
LED  SYNOPTIC  PANEL 

 

The DL2 Led shows the failures: 
 

In case of contemporary presence of more alarms, the Led indication follows the priority shown in the chart 
 

DL2 

ALARM 

Quick flashing 

Disconnected battery 

Slow flashing 

Battery resistance > 1 ohm 

On fix 

Fuse F3 (battery) interrupted 

On fix 

Fuse F8 (mains) interrupted 

Off 

None of previous failures 

 
Leds DL5, DL6 and DL7 show the current consumed by the outputs

 

Condition 

LED Status 

DL5 

DL6 

DL7 

I < 0,25 A 

OFF 

OFF 

SLOW FLASH 

0,25A < I <0,6 A 

OFF 

OFF 

FLASH 

0,6A < I <0,9A 

OFF 

OFF 

QUICK FLASH 

0,9A < I < 1,3A 

OFF 

SLOW FLASH 

FIX ON 

1,3A < I < 1,7A 

OFF 

FLASH 

FIX ON 

1,7A < I < 2,1A 

OFF 

QUICK FLASH 

FIX ON 

2,1A < I < 2,4A 

SLOW FLASH 

FIX ON 

FIX ON 

2,4A < I < 2,8A 

FLASH 

FIX ON 

FIX ON 

2,8A < I < 3A 

FIX ON 

FIX ON 

FIX ON 

OVERCHARGE I > 3A 

QUICK FLASH 

QUICK FLASH 

QUICK FLASH 

 

 

Note: SLOW FLASH = 1 Hz – FLASH  2 Hz – QUICK FLASH = 4 Hz 

 
 

 

Отзывы: