MA-SE-TF24-01-05 Manual Triade F24 rev5 

 

   Rev.4 Page 1 of 2 

 

OUT DOOR FIRE SOUNDER 

SELF-SUPPLIED SOUNDER TRIADE F24 

 

 
Features

:

 

Triade F24 sounder has been studied for acoustic and optical indication of fires. 
All materials used to manufacture it comply to fire system requirements and the housing is built in fireproof materials. 
The sounder has to be installed by qualified personnel only, respecting all installation norms and adequate distances and height so 
as to get the best optical and acoustic performances. 
  

Installation: 

Fix the sounder to the wall through the 4 holes on its base (see Pic. 1). 

Use an adapter to connect all cables in case of a system with external pipes

 
 

                     Pict

. 1

 

 
 
 
 
 
 
 
 
 
 
Connection:
 

 
Connection: with 

4 wires 

 

 

Connect the control panel output to “polarity inversion” in the sounder to terminal RL (+)  (stand-by negative) and to 
terminal RL (-) (positive in stand-by) and 24Vcc supplying for battery recharge to terminals –COM and +24V. 
Furthermore, insert the end-of-the-line resistor R between terminal RL (-) and terminal R (pict.2). The value of the R 
end-of-the-line resistor depends on the type of control panel installed and it is mentioned in the control panel manual. 

      

                    
            
            STATO A RIPOSO 
                 

     
 

 
 
                     

In case of alarm of the control panel, it will invert the inverting output,  activating the sounder whilst, if the cable is cut, the 
control panel will recognize the status change of the inverting line and will give an alarm but without triggering off the sounder 
alarm.  

 
Signalings: 

The  sounder  Triade  F24  is  managed  by  a  microprocessor  capable  to  check  the  battery  and  the  speaker.  In  case  of  anomaly  it 
sends out a negative open collector indication to terminal OUT TEST whilst the check-led on board indicates the type of failure 
according the number of flashes followed by a short pause.  

 

The microprocessor automatically performs the test of battery current each 32 days, and if not passed, it sends 3 

negative

 

pulses 

and  the  anomaly 

led

  makes  3  flashes  followed  by  a  short  pause.  Moreover,  the  microprocessor  makes    a  self-test  too  at  any 

moment and in case of failure or malfunctioning it sends out a 

negative output

 with block of the sound. 

 

Inverting output (stand-by negative) 

Positive recharge 

Negative recharge

 

-COM 

+24V 

 Inverting output (stand-by positive) 

RL(+) 

RL(-) 

Fire main 

 
 

R

 
 
  sounder 

Pict. 2 

STANDBY STATUS 

Polarity-inversion output of 
control panel 