14
Fig. 17
¾
The power cord must be positioned so that a
temperature of 75°C
will not be reached at any point.
¾
Do not use reductions, adapters or splitters since they might cause false contacts and lead to dangerous
overheating.
When the connection is made directly to the electric network:
¾
Use a device that ensures disconnection from the mains in which the contacts are opened to a distance that
permits complete disconnection according to the conditions for over-voltage category III.
¾
Remember that the ground wire must not be interrupted by the circuit-breaker.
¾
As an alternative, the electric connection can also be protected by a high-sensitivity residual current circuit-
breaker but this may be subject to nuisance tripping due to residual humidity in heating elements.
¾
It is highly recommended to attach the special green-yellow ground wire to an efficient ground system.
WARNING:
If the power cord is replaced, the ground wire (yellow-green) connected to the terminal, should
be longer than the other wires by about 2 cm.
TABLE N°4
: TYPES OF POWER CORDS
Work surface
Oven
Cross section
operation
operation
230V ~
230V 3~
400V 2N~
400V 3N~
Gas oven / Gas grill
3x0.75mm²
-
-
-
Gas oven / Electric grill
3x1mm²
-
-
-
Only gas burner
Electric Oven
3x1mm² (M6)
3x1,5mm² (M9
- - -
Ventilated
Electric
Oven 3x1,5mm²
- - -
Gas oven / Gas grill
3x1mm²
-
-
-
Gas burner + 1 hot plate
Gas oven / Electric grill
3x1,5mm² (M6)
3x2,5mm² (M9
- - -
Electric Oven
3x1,5mm² (M6)
3x2,5mm² (M9
- - -
Ventilated
Electric
Oven 3x2,5mm²
- - -
Gas burner + 2 hot plate
Forno elettrico statico
3x2,5mm²
4x1,5mm² 4x1,5mm² 5x1,5mm²
Forno elettrico ventilato multi-9
3x2,5mm²
4x1,5mm² 4x1,5mm² 5x1,5mm²
4 hot plate
Forno elettrico statico
3x2,5mm²
4x1,5mm² 4x1,5mm² 5x1,5mm²
Forno elettrico ventilato multi-9
3x2,5mm²
4x1,5mm² 4x1,5mm² 5x1,5mm²
Ceran Forno
elettrico
statico
3x2,5mm²
4x1,5mm² 4x1,5mm² 5x1,5mm²
Forno elettrico ventilato multi-9
3x4mm²
4x1,5mm² 4x1,5mm² 5x1,5mm²
ATTENTION: The appliance conforms with the regulations of directives 90/396EEC (Gas Directive) regarding gas
appliances for domestic use and the like, 93/68 and 73/23 (Low Voltage Directive) regarding electrical safety and
2004/108/CE, 93/68 and 89/336 (EMC Directive) regarding electromagnetic compatibility.
THREE-PHASE ELECTRIC CONNECTION
The cookers that can also be connected to three-phase systems normally are factory built for the single-phase 230V
connection and are supplied with a power cord. Based on the connection system used, install the power cord type
indicated in table No.4.
To use the selected connection system change the jumpers on the terminal strip as indicated in the diagram of (Fig.18)
Letter L (phase) = brown wire;
Letter N (neutral) = blue wire;
Ground symbol
= green-yellow
wire;
Содержание VEF61EG
Страница 3: ...3...
Страница 8: ...8 Table 1...
Страница 9: ...9...
Страница 10: ...10...
Страница 11: ...11...