3
1
User Manual
DIN-RAIL EMERGENCY LAMP
Read all instructions carefully
DIMENSIONS
WIRING DIAGRAM
2
Vemer S.p.A.
I - 32032 Feltre (BL) • Via Camp Lonc, 16
Tel +39 0439 80638 • Fax +39 0439 80619
e-mail: [email protected] - web site: www.vemer.it
V3IS00965-010
Mod.
Nana
Nana is an electronic emergency lamp with DIN bar installation, which lights
up in the event of a blackout to illuminate the electrical panel where it is
installed, thus facilitating the reset operation.
Nana ensures constant illumination in the electrical panel for more than two
hours thanks to the rechargeable battery with which it is equipped.
Code
Model
Description
VE771200
Nana
Emergency lamp for DIN rail - 1 module
SAFETY WARNINGS
During product installation and operation it is necessary to observe the
following instructions:
1) The product must be installed by a qualified person, in strict compliance
with the connection diagrams.
2) Do not power or connect the instrument if any part appears to be damaged.
3) The product must be installed and activated in compliance with current
electric systems standards.
4) Do not use the product for purposes other than those indicated.
5) In case of product malfunction, do not carry out any work repair and contact
technical assistance directly.
6) The product can be used in environments with overvoltage category III and
degree of pollution 2.
7) In the electrical system upstream of the product must be installed an
overcurrent protection device.
8) After installation, inaccessibility to the connection terminals without
appropriate tools must be guaranteed.
9) Before accessing the connection terminals, verify that the leads are not live
TECHNICAL SPECIFICATIONS
• Power supply: 230 Vac (-10% ÷ + 10%) 50/60 Hz
• Absorption: 3.0 VA (0.2 W)
• Backup batteries:
- 1 rechargeable (non-replaceable) NiMH 3.6V battery with 140 mAh
- complete recharge time: 48 hours
• Battery life in the absence of mains power supply: about 2 hours
• Light source:
- 1 white LED
- Luminous flux at 1 meter: 20 Lux
- Emission angle: 120 °
• Red LED for low battery indication
• DIN rail installation (occupied space: 1 module)
• Terminal block for cables with 1.5 mm2 section
• Operating temperature: 0 °C ÷ + 50 °C
• Storage temperature: -20 °C to + 50 °C
• Operating humidity: 20 ÷ 90% non-condensing
• Degree of protection: IP40
• Insulation: reinforced between accessible parts (front) and all other terminals
• The installation of the lamp Nana requires the space of one module on the
DIN rail.
• To prevent the battery from discharging or from being damaged during
storage, there is a selector on the lower part that allows you to exclude the
battery from the circuit.
For this, before installing the lamp, it is necessary to move the selector from
the
“0”
position to the
“I”
position.
• Make the connections as indicated in the wiring diagram.
• If the red LED on the front of the emergency lamp is on means that the
battery is depleted.
• The light source of this appliance is not replaceable; when the light source
reaches the end of life, the entire appliance must be replaced by qualified
personnel
REFERENCE STANDARDS
Compliance with the Community Directives:
2014/35/EU (LVD), 2014/30/EU (EMCD)
is declared in reference to the following harmonized standards:
• EN 60598-1, EN 60598-2-2
• EN 61000-6-1, EN 61000-6-3
• EN 55015, EN 61547
04-2018
4
INSTALLATION
Lamp always off (storage position)
Active lamp (lit when not powered)
33 mm
49 mm
74 mm
18 mm
90 mm