Vemer Nana Скачать руководство пользователя страница 2

3

1

User Manual

DIN-RAIL EMERGENCY LAMP

 

Read all instructions carefully

DIMENSIONS

WIRING DIAGRAM

2

Vemer S.p.A.

I - 32032 Feltre (BL) • Via Camp Lonc, 16

Tel +39 0439 80638 • Fax +39 0439 80619
e-mail: [email protected]  -  web site: www.vemer.it 

V3IS00965-010

 

Mod.

 Nana

Nana is an electronic emergency lamp with DIN bar installation, which lights 
up in the event of a blackout to illuminate the electrical panel where it is 
installed, thus facilitating the reset operation.
Nana ensures constant illumination in the electrical panel for more than two 
hours thanks to the rechargeable battery with which it is equipped. 

Code  

Model 

Description

VE771200

 

Nana 

Emergency lamp for DIN rail - 1 module

SAFETY WARNINGS

 

 During product installation and operation it is necessary to observe the 
following instructions:

1)    The product must be installed by a qualified person, in strict compliance 

with the connection diagrams.

2)   Do not power or connect the instrument if any part appears to be damaged.
3)    The product must be installed and activated in compliance with current 

electric systems standards.

4)    Do not use the product for purposes other than those indicated.
5)    In case of product malfunction, do not carry out any work repair and contact 

technical assistance directly.

6)    The product can be used in environments with overvoltage category III and 

degree of pollution 2.

7)    In the electrical system upstream of the product must be installed an 

overcurrent protection device.

8)    After installation, inaccessibility to the connection terminals without 

appropriate tools must be guaranteed.

9)   Before accessing the connection terminals, verify that the leads are not live

TECHNICAL SPECIFICATIONS

•   Power supply: 230 Vac (-10% ÷ + 10%) 50/60 Hz
•   Absorption: 3.0 VA (0.2 W)
•   Backup batteries:
  - 1 rechargeable (non-replaceable) NiMH 3.6V battery with 140 mAh
  - complete recharge time: 48 hours
•   Battery life in the absence of mains power supply: about 2 hours
•   Light source:
  - 1 white LED
  - Luminous flux at 1 meter: 20 Lux
  - Emission angle: 120 °
•   Red LED for low battery indication
•   DIN rail installation (occupied space: 1 module)
•   Terminal block for cables with 1.5 mm2 section
•   Operating temperature: 0 °C ÷ + 50 °C
•   Storage temperature: -20 °C to + 50 °C
•   Operating humidity: 20 ÷ 90% non-condensing
•   Degree of protection: IP40
•   Insulation: reinforced between accessible parts (front) and all other terminals

•    The installation of the lamp Nana requires the space of one module on the 

DIN rail.

•    To prevent the battery from discharging or from being damaged during 

storage, there is a selector on the lower part that allows you to exclude the 

battery from the circuit.

   For this, before installing the lamp, it is necessary to move the selector from 

the 

“0”

 position to the 

“I”

 position.

 

•   Make the connections as indicated in the wiring diagram.
•    If the red LED on the front of the emergency lamp is on means that the 

battery is depleted.

•    The light source of this appliance is not replaceable; when the light source 

reaches the end of life, the entire appliance must be replaced by qualified 

personnel

REFERENCE STANDARDS

Compliance with the Community Directives:

2014/35/EU (LVD), 2014/30/EU (EMCD)

is declared in reference to the following harmonized standards:

• EN 60598-1, EN 60598-2-2

• EN 61000-6-1, EN 61000-6-3

• EN 55015, EN 61547

04-2018

4

INSTALLATION

Lamp always off (storage position)
 Active lamp (lit when not powered)

33 mm

49 mm

74 mm

18 mm

90 mm