- 42 - 

Iride Chronothermostat User Manual

BATTERY REPLACEMENT

The model Iride (batteries) signals the status of depleted batteries switching on the 
symbol 

 (field 

(10)

) and making the display to flash.

In this status the regulation is always guaranteed, but it’s advisable to replace the 
batteries as soon as possible! (*)

If the charge level of batteries further decreases, the chronothermostat enters into less 
consumption mode, it switches off the display and it doesn’t perform any regulation.

(*) Remove the depleted batteries and replace them with the new ones in a maximum 
time of one minute (charge reserve) to avoid to lose the settings of date and time 
(the performed programmings on the contrary remain memorized even if this limit is 
surpassed).

Attention: after batteries replacement, the display will switch on within 15 

seconds at max.

  

Dispose of the used batteries observing the 

laws in force in relation to the disposal 

of hazardous waste

The removal of the device occurs 

by pulling on the convexity of the frame

(see figure).

DEVICE RESET

If you want to erase all performed settings and to recharge the default values, proceed 
as follows:

1.   to switch off and to switch on the power of the chronothermostat (230 V versions) 

or to extract the chronothermostat from the wall-mounted base and reinsert it 
(battery versions)

2.   during the flashing of the keys press the key 

 until the display shows the writing 

dEF

.

 
Default values are indicated on page 42 of this manual.

English

Содержание Iride

Страница 1: ...Chronothermostat IRIDE User Manual...

Страница 2: ......

Страница 3: ...fication Page 23 Temperatures T1 T2 T3 modification Page 24 Timing setting Page 26 Advanced functions menu Page 27 Manual operation Page 30 Off operation Page 31 Backlighting management Page 33 Minimu...

Страница 4: ...al input for the connection of a telephone dialler for switches on and switches off of the device remotely Summer and winter operating mode Front panels of white and anthracite grey colour included in...

Страница 5: ...ONNECTION DIAGRAM Chronothermostat frames and plastic elements available in white and anthracite grey colors frames mount A mount B plastic elements VI plastic elements BM COM NA NC N L 230V Iride 230...

Страница 6: ...4 Iride Chronothermostat User Manual BATTERY IRIDE MOUNTING A Bticino Living series Light Light Tech Livinglight Axolute Vimar Eikon series Eikon Evo Plana Ave S44 series ABB Mylos series English...

Страница 7: ...5 Iride Chronothermostat User Manual IRIDE 230 MOUNTING Bticino Living series Light Light Tech Livinglight Axolute Vimar Eikon series Eikon Evo Plana Ave S44 series ABB Mylos series A English...

Страница 8: ...6 Iride Chronothermostat User Manual BATTERY IRIDE MOUNTING ABB Chiara series Vimar Ark series B English...

Страница 9: ...7 Iride Chronothermostat User Manual IRIDE 230 MOUNTING ABB Chiara series Vimar Ark series B English...

Страница 10: ...8 Iride Chronothermostat User Manual BATTERY IRIDE MOUNTING Gewiss Chorus series B Remove the cogs English...

Страница 11: ...9 Iride Chronothermostat User Manual IRIDE 230 MOUNTING Gewiss Chorus series B Remove the cogs English...

Страница 12: ...10 Iride Chronothermostat User Manual BATTERY IRIDE MOUNTING Bticino Matix series B BM Remove the cogs English...

Страница 13: ...11 Iride Chronothermostat User Manual IRIDE 230 MOUNTING Bticino Matix series B BM Remove the cogs English...

Страница 14: ...12 Iride Chronothermostat User Manual BATTERY IRIDE MOUNTING Vimar Idea series VI B English...

Страница 15: ...13 Iride Chronothermostat User Manual IRIDE 230 MOUNTING Vimar Idea series VI B English...

Страница 16: ...al BATTERY IRIDE MOUNTING Bticino Livinglight AIR series AIR Note if the box extension is not present adapter which increases the depth of the flush mounting box we recommend you using the frame for L...

Страница 17: ...nual IRIDE 230 MOUNTING Bticino Livinglight AIR series AIR Note if the box extension is not present adapter which increases the depth of the flush mounting box we recommend you using the frame for Liv...

Страница 18: ...16 Iride Chronothermostat User Manual BATTERY IRIDE MOUNTING Bticino Livinglight AIR series AXO AIR Mount AXO AIR is not included in the package English...

Страница 19: ...17 Iride Chronothermostat User Manual IRIDE 230 MOUNTING Bticino Livinglight AIR series AXO AIR Mount AXO AIR is not included in the package English...

Страница 20: ...protection device from the overcurrents must be present for Iride 230 models only Code Model Description VE456000 Iride Touch screen chronothermostat batteries VE457800 Iride 230 Touch screen chronoth...

Страница 21: ...or power supply Temperature regulation On off with hysteresis setting between 0 1 C and 1 C Proportional with settable band and period Summer winter operating mode Weekly programming 7 programs availa...

Страница 22: ...ogramming menu not used not used Time and minutes Load activation in summer mode cooling Manual operation activation Load activation in winter mode heating Measured environment temperature Program on...

Страница 23: ...display To clean the display use a soft lint free cloth without using excess force INSTALLATION The chronothermostats of Iride series are designed for flush mountig on 3 modules box 503 type The chron...

Страница 24: ...setting Day setting the diagram adjustable cover plates and they are mount A mount B according to the needs it could be necessary to remove the side cogs mount AIR couple of side BM plastic elements...

Страница 25: ...the graphic of the program on Attention To operate correctly the chronothermostat requires the time and date insertion If once mains powered no value is set within about 30 seconds the chronothermost...

Страница 26: ...arts flashing Parameters sequence to set is seconds minutes hours year month day 3 Use the keys and to modify the values and the key to confirm moving to the next parameter for seconds it s possible o...

Страница 27: ...ntil the symbol flashes and press the key to access the parameters modification 3 The programs page is displayed the first day of the week DAY 1 flashing the current program for example P1 of the curr...

Страница 28: ...and the delay and press the key to move to the next hour 4 When the program satisfies the user s needs go back to the days pressing twice the key and repeat for the other days of the week the operatio...

Страница 29: ...The value of the flashing T3 temperature is displayed Modify the value with the key and and press the key to go back to the page of T1 temperature 6 Once all parameters are set to exit and to go back...

Страница 30: ...e measurement unit change hours and days 4 The measurement unit starts flashing h0ur or day Press the keys and to choose a timing in hours h0ur or days day Timing setting This menu allows the setting...

Страница 31: ...following operation parameters operating mode heating or cooling regulation type on off or proportional parameters relative to regulation type antifreeze temperature password for key lock system oper...

Страница 32: ...ating and summer cooling For further information about the operating mode see the chapter Regulation type on page 36 Regulation type only for heating mode For heating mode it s possible to choose betw...

Страница 33: ...it s possible to set a safety temperature antifreeze temperature 0ff to maintain also if the chronothermostat is switched off It s possible to choose a value between 1 C and 10 C It s also possible to...

Страница 34: ...tion the chronothermostat performs as a normal thermostat adjusting on the basis of the Tm temperature manual setpoint independently from the day and the time where it is The manual operation is signa...

Страница 35: ...maintains a minimum temperature Toff antifreeze temperature to avoid the freezing of the systems where the device is installed Toff can have values between 1 C and 10 C or it can be completely shut d...

Страница 36: ...mal operation according to the set programming closed chronothermostat in off mode Remotely off status is displayed with the flash of the symbol on field 9 to differentiate it from the keyboard off st...

Страница 37: ...es following the difference between the measured temperature and the programmed setpoint In particular it will be blue if the measured temperature is lower than the programmed setpoint of at least 0 5...

Страница 38: ...cks during the summer period in order to prolong the lighting time in the late afternoon to the loss of the early morning In European countries summer time starts the last Sunday of march and ends the...

Страница 39: ...is displayed indicated with the symbol In the example a the Sunday 7 of the last week LA of march 03 at 2 o clock 02 b if it s necessary change the parameters with the keys and and move to the next p...

Страница 40: ...increasing heating mode cooling mode where SET represents the setpoint and DIFF the hysteresis useful to avoid continuous switches on switches off dangerous for the system in proximity to the reaching...

Страница 41: ...tion period is passed the device compares again the environment temperature with the setpoint and it updates the activation and deactivation times for the new period The result of the proportional reg...

Страница 42: ...end of the timing operation will then switched to automatic mode Emergency regulation winter mode only The device performs a regulation of emergency if an error occurs during the reading of the probe...

Страница 43: ...ted in minutes and for this reason if for example you set a timing of 3 days at 12 15 on Tuesday it will expire at 12 15 on Friday Attention the timings can end before their programmed expiration if o...

Страница 44: ...ate and time the performed programmings on the contrary remain memorized even if this limit is surpassed Attention after batteries replacement the display will switch on within 15 seconds at max Dispo...

Страница 45: ...de Chronothermostat User Manual REFERENCE STANDARDS Compliance with Community Directives 2014 35 EU LVD 2014 30 EU EMCD is declared in reference to the harmonized standards EN 60730 2 7 EN 60730 2 9 E...

Страница 46: ...0 C 0 1 C 25 0 C antifreeze temperature 1 0 C 10 0 C 0 1 C 6 0 C operating mode winter summer winter regulation type ON OFF PROP ON OFF ON OFF hysteresis 0 1 C 1 0 C 0 1 C 0 3 C proportional band 0 5...

Страница 47: ...19 20 21 22 23 P3 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P4 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P5 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 1...

Страница 48: ...19 20 21 22 23 P3 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P4 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P5 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 1...

Страница 49: ......

Страница 50: ......

Страница 51: ......

Страница 52: ...V3IS00684 014 Vemer S p A I 32032 Feltre BL Via Camp Lonc 16 Tel 39 0439 80638 Fax 39 0439 80619 e mail info vemer it web site www vemer it 06 2017...

Отзывы: