Set - Diff (R) - ZN
R
ON
OFF
Set
D
Set + Diff (D) + ZN
ZN
ZN
Set 1
D
ON
OFF
Diff. 1
OUT 1
Set 1
D
ON
OFF
Diff. 1
OUT 1
D
OUT 2
Set 1
R
ON
OFF
Diff. 1
OUT 2
R
OUT 1
Set 1
R
ON
OFF
Diff. 1
OUT 1
Set - Diff (R) - ZN
R
ON
OFF
Set
D
Set + Diff (D) + ZN
ZN
ZN
English
Dead band Mode
Temperature
PWM Mode
Temperature
Mode PRO=0
1 output
2 outputs
Mode PRO=1
1 output
2 outputs
- 34 -
User Manual – Thermoregulator FHT
No output is activated within
the dead band; outside
the dead band the device
operates by
direct
action
if the parameter controlled
increases and by
reverse
action if it decreases.
PWM operating mode
(time-controlled proportionate)
• Dead-band operation
featuring relays activated
periodically by impulse
(settable timing, see Output
menu).
The PWM mode modulates
the power based on the
position of the parameter
within the differential (power
increases as deviation from
set-point increases).
Warning: Not recommended for use with compressors, as this would cause
short start/stop periods.
Direct operating mode [PRO=0]
• When in this mode, all outputs
operate in
direct
.
Set-point
1
[ST1]
and
differential 1
[DF1]
must be
assigned values.
Hysteresis is to the right of
the set-point.
If both outputs are used, the
hysteresis of each output is
equal to half of the differential.
In this case output 1 will turn on when the parameter measured reaches value
[ST1]+[DF1]/2
; output 2 will turn off on reaching this value.
Reverse
operating mode [PRO=1]
• When in this mode, all outputs
operate in
reverse
.
Set-point
1
[ST1]
and
differential 1
[DF1]
must be
assigned values.
Hysteresis is to the left of the
set-point.