background image

95

110332-02 - 6/22

PHTM II

 Installation, Operating & Service Instructions

Appendix B 

Water Quality and Boiler Additives

The heat exchanger used in this boiler is made 

from stainless steel coils having relatively narrow 

waterways. Once filled with water, it will be subjected 

to effects of corrosion as well as fouling from any 

debris introduced from the system. Take the following 

precautions to minimize chance of severe heat 

exchanger damage caused by corrosion and/or 

overheating.
1. 

Flush system before connecting boiler.

 

In a replacement installation, flushing system will 

remove impurities, such as sediment, solder flux, 

metal shavings and traces of old boiler additives. 

Even if system is new, do not omit this step – new 

systems will contain flux and may even contain 

other impurities listed above. 

 

Flush system completely and repeat if necessary 

to completely remove these contaminants. If 

necessary, a cleaning agent may be used to 

assist in system cleaning. See Section 14 Start-up 

and Checkout for recommended cleaners.

2. 

Make sure the system is tight-

 

this is the single most important guideline. 

 

Tap water contains dissolved oxygen which 

causes corrosion. In a tight system, this oxygen 

comes out of solution and is quickly removed from 

system through automatic air vent. System then 

remains essentially free of oxygen. 

 

If system is not tight, however, frequent additions 

of make-up water can expose heat exchanger 

to oxygen on a continuous basis. In addition, 

frequent additions of hard make-up water 

can cause calcium deposits to collect in heat 

exchanger, causing severe damage. To minimize 

additions of make-up water.

 

A.  Inspect system thoroughly for leaks before  

 

putting it into service.

 

B.  If system includes underground piping    

 

or other piping in which a leak might go   

 

undetected, consider isolating boiler from the  

 

system with a heat exchanger.

 

C.  Make sure expansion tank is properly sized  

 

and in good condition, if it is not, safety relief  

 

valve may open frequently, resulting in regular  

 

additions of make-up water.

 

D.  If an automatic fill valve is installed,  

 

 

installation of a water meter in fill line is   

 

strongly recommended so routine additions  

 

of make-up water can be detected and their  

 

cause corrected.

3. 

Non-metallic tubing

 - even if system is tight, 

oxygen can be introduced into system through 

some types of non-metallic tubing used in radiant 

or snow melt systems.

 

Other non-metallic tubing is equipped with an 

oxygen barrier to prevent migration of oxygen 

into water. If boiler is to be installed in a system 

containing non-metallic tubing without an oxygen 

barrier, it must be isolated from boiler with a heat 

exchanger.

4.  Water chemistry, antifreeze, and boiler water 

additives – improper boiler water chemistry can 

cause the heat exchanger damage described 

above, as well as deterioration.

5.  Avoid use of petroleum based boiler additives 

and ester-based oils/lubricants. These can attack 

seals in both boiler and system.

Freeze Protection

If this freeze protection is required, use the following 
or its equivalent:

 

A.  Fernox Alphi-11

 

B.  Sentinel X500 Inhibited Polypropylene Glycol

1.  Refer to antifreeze manufacturer’s instructions 

for required dosage. In general these products 

are a blend of glycol (for freeze protection) and 

inhibitors (to protect glycol from attacking metallic 

system components.

2.  Do not add any more antifreeze than is necessary 

to protect system from freeze damage.

3.  Maximum antifreeze concentration 50%.

4.  Test antifreeze and inhibitor concentration 

annually.

 

A.  Inhibitor concentration test kit for Fernox  

 

Protector F1, 25 tests per kit. P/N 101148-01.

 

B.  Inhibitor, Fernox Protector F1, 1 pint (500 mL)  

 

P/N 101147-01.

5.  Allowance must be made for additional expansion 

of glycol solution.

6.  Fernox products are available from: 
 

Alent PLC Consumer Products Division 

 

4100 6th Avenue

 

Altoona, PA 16602

 

Tel: (972) 547-6002

 

Email: [email protected]

7.  Sentinel products are available from: 
 

Douglas Products and Packaging

 

1550 E. Old 210 Highway

 

Liberty, MO 64068

 

Tel: (877) 567-2560 (Toll Free) and/or selected 

HVAC distributors

Содержание PHANTOM II PHTM2120H

Страница 1: ...5 Locating Boiler 8 6 Preparing Boiler 12 7 General Venting 15 8 Sidewall Direct Venting 22 9 Vertical Direct Venting 28 10 Heating System Piping 34 11 Gas Piping 41 12 Field Wiring 42 13 Condensate D...

Страница 2: ...or serious injury DANGER Explosion Hazard DO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance If you smell gas vapors DO NOT try to operate...

Страница 3: ...uction flue products and fuel contain alumina silica heavy metals carbon monoxide nitrogen oxides and or other toxic or harmful substances that can be hazardous to health and life and that are known t...

Страница 4: ...deadly gas that may be introduced into your home by any malfunctioning fuel burning product or vent system failure It is strongly recommended that CO alarms be installed near bedrooms and on all leve...

Страница 5: ...for altitude conversion instructions For part no containing S i e PHTM2180CNG1SUA0 boiler is listed for 0 to 2 000 ft 610 m Do not install above 2 000 ft 610 m Model Number Shipping Weight lb kg Empty...

Страница 6: ...ge connection board Provides field connections for thermostats external limits remote firing devices 4 20mA or 0 10V header sensor outdoor sensor and LWCO 9 Control enclosure Houses boiler control and...

Страница 7: ...7 110332 02 6 22 PHTM II Installation Operating Service Instructions 4 How It Works continued Figure 4 1 How It Works 1 2 4 3 12 17 13 15 8 7 9 11 14 10...

Страница 8: ...location Manufacturer will not be held responsible for water damage resulting from this appliance or any of its components 5 Check for and remove any combustible materials gasoline or other flammable...

Страница 9: ...pening within 12 in 305 mm of floor Minimum free area 100 in 2 650 cm2 for each opening This free area takes into account blocking effect of grills and louvers If using screens minimum screen size 1 4...

Страница 10: ...taminants to avoid Spray cans containing chloro fluorocarbons CFC s Permanent wave solutions Chlorinated waxes cleaners Chlorine based swimming pool chemicals Calcium chloride used for thawing Sodium...

Страница 11: ...n which the appliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appliance not connected to the common venting system...

Страница 12: ...4 Fiber Vent Connector Temp Pressure Gauge Lag Screw 4X Screw 4X Drain Valve Safety Relief Valve Gas Shutoff Valve Washer 4X Circulator Circulator Flange 2X REV EN A 103 143 A B 4 4 3 3 2 2 TITLE FIR...

Страница 13: ...alled vent reducer 3 in to 2 in could cause unreliable operation at elevated carbon monoxide levels resulting in severe personal injury death or substantial property damage 3 Lubricate heat exchanger...

Страница 14: ...and attach bracket using provided 5 16 in x 2 in lag screws and washers For wood studs with drywall or paneling greater than 1 2 in 12 mm thick metal studs or masonry wall use anchors suitable for boi...

Страница 15: ...ection 8 for details Figure 7 3 Sidewall Concentric Termination see Section 8 for details Direct Vent Sidewall Termination Options Direct Vent Vertical Termination Options Figure 7 4 Vertical Terminat...

Страница 16: ...shed vent and air piping to ensure air tightness and compliance with provided instructions and code requirements Do not mix components from different venting systems Covering non metallic vent pipe an...

Страница 17: ...e following or equivalent may be used to join CPVC to PVC A Primer IPS P 70 B Cement IPS 790 Material Standard Vent Pipe CPVC sched 40 or 80 ASTM F441 PVC sched 40 or 80 ASTM D1785 PVC DWV ASTM D2665...

Страница 18: ...ebur inside and outside of pipe ends after cutting 11 Dry fit all vent and air components before cementing any joints 12 Use field supplied primer and cement appropriate for materials being joined Fol...

Страница 19: ...th of straight run between anchors X Loop horizontal only top view Y 5 6 150mm Min 6 150mm Min 2Y 5 7 General Venting continued Figure 7 15 CPVC PVC Venting Expansion Loops Figure 7 14 PVC Venting Wal...

Страница 20: ...gths of elbows and fittings 5 Only cut polypropylene vent pipe as permitted by vent manufacturer and in accordance with their instructions Ensure cut end is square and deburred prior to assembly 6 Boi...

Страница 21: ...PF LB or 4PF LB Increaser 2 in 60 mm to 3 in 80 mm 2PPS X3L ISIA0203 2PF 2I3 PF LB locking band PVC to PP Adapter 2 in 60 mm 2PPS ADL ISAGL0202 adapter IAFC02 clamp N A Table 7 17 Listed Polypropylen...

Страница 22: ...h as stones or balls or subject to buildup of leaves or dirt 4 Maintain clearances to vent terminal per Figure 8 1 A Minimum 12 in 305 mm from any door window or other gravity air inlet B Minimum 3 ft...

Страница 23: ...23 110332 02 6 22 PHTM II Installation Operating Service Instructions 8 Sidewall Direct Venting continued Figure 8 1 Vent Terminal Clearances Air Terminal not Shown for Clarity...

Страница 24: ...If venting with polypropylene i Use UV resistant or UV stabilized components for all exterior pipe and fittings ii Remove gasket from terminal fitting to install screen 6 Brace exterior vertical runs...

Страница 25: ...ble 7 11 Figure 8 8 Low Profile Terminal Grade or Snow line From boiler vent connection Possible Orientations 12 305mm Min To boiler air connection Gra Sno Possible Orientations To boile air connec Du...

Страница 26: ...NG Asphyxiation Hazard If vent system is too short to accommodate required 30 in 760 mm of CPVC pipe and CPVC elbow between boiler and PVC venting use listed CPVC terminal kit Failure to comply could...

Страница 27: ...0 mm 3PPS HKC ICWT352 terminal ICCT3503 two pipe adapter 3PF HCT terminal 3PF CTA two pipe adapter Polypropylene Concentric Sidewall Terminal DuraVent shown From boiler vent connection 12 305mm Min Gr...

Страница 28: ...al arrangement with vertical vent and sidewall air intake is permitted See Figure 9 5 9Vertical Direct Venting WARNING Asphyxiation Hazard Follow these instructions when determining vent terminal loca...

Страница 29: ...al Fittings DuraVent PolyPro Centrotherm InnoFlue Selkirk PolyFlue UV resistant single wall pipe 2PPS BG screen UV stabilized end pipe IASPP02 screen UV resistant pipe 2PF HVST screen Figure 9 5 Alter...

Страница 30: ...Figure 9 7 for assembly Figure 9 6 CPVC PVC Concentric Terminal 9Vertical Direct Venting continued From boiler vent connection To boiler air connection 12 305mm Min USA 18 460mm Min Canada 24 610mm M...

Страница 31: ...rt PVC adapter and install electrical conduit locknut to secure Seal all joints with RTV silicone B DuraVent InstallPolyProlowerB ventadapter in base of tee C Centrotherm Install cap in base of tee Ro...

Страница 32: ...adapter See Text Flex Male Adapter 10 3 1m 24 610mm Min 12 305mm Min Boiler Notes 1 All B Vent joints must be sealed with RTV 2 Seal the Flex Male Adapter to the inside of the lower B Vent Adapter wit...

Страница 33: ...ct Venting continued Table 9 15 Polypropylene Masonry Chimney Chase Components DuraVent PolyPro Centrotherm InnoFlue Selkirk PolyFlue 2PPS FKC chimney kit 2PPS FLEX flex length IFCK02 chimney kit with...

Страница 34: ...amage if valve opens The end of discharge pipe must terminate in unthreaded pipe C If safety relief valve discharge is not piped to drain it must terminate within 6 in 150 mm of floor D Do not route d...

Страница 35: ...tem Piping continued 4 Expansion tank required A Ifthisboilerisreplacinganexistingboilerwith no other changes in system old expansion tank can generally be reused B If expansion tank must be replaced...

Страница 36: ...local jurisdiction A Protection of this boiler against low water and or inadequate flow is provided by UL353 listed flow switch built into boiler B Thisisawatertubeboilerandthisflowswitch is therefor...

Страница 37: ...BER MATERIAL ALTA NEAR BOILER PIPING PRIMARY SECONDARY HEAT ONLY DES E CHK APVD DATE DRAW 09 UNLESS OTHERWISE NOTED ALL DIMENSIONS IN INCHES TOLERANCES X X 1 X XXX 005 X XX 03 ANGLE 1 PROPERTY OF U S...

Страница 38: ...USE ITEM NUMBER MATERIAL ALTA NEAR BOILER PIPING PRIMARY SECONDARY W INDIRECT WATER HEATER DES EJL CHK APVD SCALE 1 15 SIZE B SHEET 1 OF 1 DATE REVISION DRAWING NUMBER 09 13 2021 TS 103 66 A UNLESS O...

Страница 39: ...PING PRIMARY SECONDARY W HEADER HEAT ONLY DES EJ CHK APVD DATE DRAWI 01 UNLESS OTHERWISE NOTED ALL DIMENSIONS IN INCHES TOLERANCES X X 1 X XXX 005 X XX 03 ANGLE 1 PROPERTY OF U S Boiler Company Inc LA...

Страница 40: ...nc LANCASTER PA THIS DOCUMENT CONTAINS CONFIDENTIAL INFORMATION AND ITS CONTENTS ARE THE SOLE PROPERTY OF U S BOILER COMPANY INC ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION O...

Страница 41: ...NSI Z223 1 National Fuel Gas Code and or CAN CSA B149 1 Natural Gas and Propane Installation code Figure 11 1 shows typical gas piping and connection to boiler A Use thread compound compatible with li...

Страница 42: ...nal strip locations are shown in Figure 12 1 To access terminal strips 1 Remove front door Front door is removed by first loosening two thumb screws located under front of door 2 Disconnect igniter wi...

Страница 43: ...Outdoor Temperature Sensor 1 Outdoor Sensor Optional Outdoor Temperature Sensor 2 Available when Lead Lag Master Enabled Figure 12 2 120 VAC Connections Low Voltage Connections Figure 12 3 Low Voltag...

Страница 44: ...n from sun iv Avoid placing sensor near potential sources of electrical noise such as transformers power lines and fluorescent lighting v Wire sensor to boiler using minimum 22 AWG wire vi Where elect...

Страница 45: ...ilable from manufacturer B Do not route or terminate condensate drain line piping through an area that is prone to freezing temperatures or that could be damaged by leaking condensate C If point of co...

Страница 46: ...system which could result in property damage Freeze Protection If freeze protection is required see Appendix B for additional information Fill Water System WARNING Burn Hazard Never exceed maximum all...

Страница 47: ...afe place away from controls before opening vent A Use 1 4 in 6 mm ID tubing connected to hose barb and route tubing to a safe draining location B Turn vent counter clockwise and allow heat exchanger...

Страница 48: ...ld menu for 3 seconds Press or buttons until PAS is visible and press enter Press enter button while PA1 is visible Press or buttons until password 86 is reachedandpress enter Pressandholdfor five sec...

Страница 49: ...nce This soft lockout can be reset by interrupting power to boiler 5 Once a flame has been established for first time subsequent calls for burner operation should result in a flame on first try 9 Chec...

Страница 50: ...bove 50 firing rate Ensure door is sealed before taking combustion readings C For altitudes 0 to 2 000 ft 0 to 610 m CO should not exceed 200 ppm air free For altitudes above 2 000 ft 610 m CO should...

Страница 51: ...clencher un incendie ou une explosion entra nant des dommages des blessures ou la mort A Cet appareil ne comporte pas de veilleuse Il est muni d un dispositif d allumage qui allume automatiquement le...

Страница 52: ...at Status Calibration Burner On Pump s On After burner is started a Calibration is initiated due to 1 Power Cycle 2 Periodic requirement Calibration after blower reaches calibration speed setting ioni...

Страница 53: ...al Heat demand is present Visible when DHW demand is present Icon will flash if DHW setpoint is being adjusted Visible when burner is firing Icon adjacent to active priority Combi boilers only Visible...

Страница 54: ...Firing Rate rUn Run Time Hours CYC Boiler Cycles H Hold or Warning Condition E Manual Reset Lockout Not available with local user display The STA status display code contains below listed values Table...

Страница 55: ...ld history records b01 is latest entry Figure 15 7 Adjusting Parameters Menu c c Diagnostic Menu Table 15 9 Diagnostic Menu Display Description C01 Active Detailed Fault Code see Table 18 6 C02 Demand...

Страница 56: ...for 5 seconds enables adjustment by increments of 10 Press enter to accept value password only Pressing menu to exit Navigating Menus Entering password in Adjust Mode allows access to shaded menus be...

Страница 57: ...ion to LP Gas is required refer to manual Section 14 Startup and Checkout for complete instructions 0 Natural Gas 1 LP Gas 0 0 A07 A07 Altitude Selection visible only after password entered Boiler is...

Страница 58: ...ation rate during a CH1 demand Heat T stat input If rated input of installed home radiation is less than maximum output of boiler change F03 setting to limit boiler output accordingly 100 0 100 F04 F0...

Страница 59: ...ng this parameter 130 F 54 C 50 F to 180 F 10 C to 83 C 504 504 Central Heat 2 Min Boiler Water Temp Sets a low limit for Reset setpoint Set this parameter to lowest supply water temperature that will...

Страница 60: ...oiler Pump Header Sensor Demand Pump runs when boiler is firing and when there is a DHW heat demand Selected when Header Sensor is selected as CH1 and CH2 modulation sensor and boiler is a stand alone...

Страница 61: ...or Reset is Enabled boiler will automatically adjust heating zone setpoint temperature based on outdoor reset curve On Enable calculate temperature setpoint based on outdoor temperature using a reset...

Страница 62: ...fter not being used for longer than 7 days This helps prevent pump rotor seizing 7 Pump Air Elimination Pump Purge Pump purge is entered when power is cycled or when there has been an over temperature...

Страница 63: ...eeds 63 F 35 C a forced boiler recycle results Boiler will restart automatically once temperature difference has decreased and minimum off time has expired 3 Return Temperature Higher Than Supply Temp...

Страница 64: ...f an ignition failure the control retries 2 times and then goes into soft lockout for one hour After a one hour soft lockout control will retry 2 additional times before control activates a manual res...

Страница 65: ...gas inlet pressure tapping Performed combustion test Screw cap in vent adapter No errors or holds present on display Tested additional field installed controls for functionality outlined by manufactu...

Страница 66: ...clothing that is sufficiently tight around potential entry points for RCF dust 3 Gloves 4 Eye protection such as goggles safety glasses with side shields or full facepiece Take steps to assure adequat...

Страница 67: ...steps are not performed at the intervals specified 1 Inspect vent piping and air intake piping to verify it is free from leakage and deterioration Also verify vent and air intake terminals are unobst...

Страница 68: ...17 4 WARNING Asphyxiation Hazard Do not operate boiler without condensate trap ball and ball support in place Doing so could cause products of combustion and or carbon monoxide to enter building resul...

Страница 69: ...d during this inspection and for details on supporting pitching and terminating vent system 12 Inspect hydronic system A Look for leaks and repair if found If system contains antifreeze or other addit...

Страница 70: ...StA 1 temperature is above setpoint Check temperature setpoint setting Faucet icon is on Servicing DHW demand Boiler is in Warm Weather Shutdown Status StA 14 Feature not available with local user di...

Страница 71: ...rol fuel gas selection A06 0 for Natural Gas 1 for LP C Control altitude selection A07 for 0 0 to 2 000 ft 0 to 610 m 1 2 001 to 6 000 ft 611 to 1 828 m 2 6 001 to 8 000 ft 1 829 to 2 438 m 3 8 001 to...

Страница 72: ...re overshoot if heating load is too small 7 Rate Limit Firing rate is being limited due to an abnormal condition such as High Supply water temperature High Differential Water temperature High Flue Gas...

Страница 73: ...remain close to Fan Speed Demanded Large differences may mean there is a problem with blower C05 3 way valve status 0 DHW 1 CH Combi boilers only C06 System Pump On Off Status Pump status indicate co...

Страница 74: ...cally after the minimum off time Anti Short Cycle Time 1 1 Urgent calibration cooling delay Urgent calibration demand present waiting for supply temperature to decrease Boiler will start after supply...

Страница 75: ...cessary Replace pump if necessary Heating load at time of error below minimum firing rate of boiler Test individual zones and ensure proper zone sizes Header sensor not sensing temperature Boiler is m...

Страница 76: ...ture difference between dual elements too high Measure resistance of each thermistor and compare refer to sensor temperature vs resistance Table 18 7 Replace sensor if necessary H11 E11 Flue Sensor Fa...

Страница 77: ...election A06 on local display and power is cycled too fast select original fuel to clear alarm before reselecting desired fuel 17 8 BCC is missing has incompatible software revision or is damaged Remo...

Страница 78: ...ot available with local user display Check CH 20 mA Water Temperature is greater than CH 4 mA Water Temperature 18 6 Invalid Recirc Comfort Mode configuration Feature not available with local user dis...

Страница 79: ...ntinued Detailed Fault Code found on b and c menus in brackets e g 1 0 Code Name Possible Cause Corrective Action H22 E22 No Flame At Ignition No gas insufficient gas supply pressure Verify no air in...

Страница 80: ...ch peer to peer boiler has a unique slave address between 1 and 8 30 1 Sequencer slave has lost communication with Sequencer Master master header sensor failure Check boiler to boiler connection wirin...

Страница 81: ...contact is closed when it should be open H06 E06 H06 0 Hold Flue gas sensor detected temperatures in excess of 194 F 90 C or when used preferred Stack Flue Limit minus 10 E06 1 Lockout Flue gas senso...

Страница 82: ...5 Warning Invalid Setpoint interpolation parameters H18 6 Hold Invalid Recirc Comfort Mode configuration E18 7 Lockout Selected boiler model default parameters not available H18 8 Hold Boiler pump ou...

Страница 83: ...ault Missing calibration Calibration not carried out although required calibration counter reached zero check why calibration management did not work H26 3 Warning Emergency stop The burner had to be...

Страница 84: ...00 86 30 8056 104 40 5324 122 50 3599 140 60 2483 158 70 1748 176 80 1252 194 90 912 212 100 674 230 110 506 248 120 384 Table 18 8 Outdoor Air Temperature Sensor Temperature versus Resistance 10 kOhm...

Страница 85: ...85 110332 02 6 22 PHTM II Installation Operating Service Instructions 19 Internal Wiring Diagrams Figure 19 1 Ladder Diagram...

Страница 86: ...86 110332 02 6 22 PHTM II Installation Operating Service Instructions 19 Internal Wiring Diagrams continued Figure 19 2 Wiring Schematic Diagram...

Страница 87: ...87 110332 02 6 22 PHTM II Installation Operating Service Instructions Figure 19 2 Wiring Schematic Diagram continued 19 Internal Wiring Diagrams continued...

Страница 88: ...or Gasket 110880 01 6 7 Burner Door Assembly includes burner ignitor flame sensor gasket and hardware 110575 01 111560 01 8A 8B 8C Ignitor Flame Sensor includes sensor gasket and hardware 111423 01 8B...

Страница 89: ...10B 10A 16 11B 12 13 11A 120 MBH 11A 80 150 180 MBH 17 15 14 A A B B 2 1 TITLE FIRST USE ITEM NUMBER MATERIAL ALTA SERVICE PARTS WATER PIPING COMPONENTS DES EJL CHK APVD SCALE 1 5 SIZE A SHEET 1 OF 1...

Страница 90: ...Gas piping with gaskets o rings and hardware 110588 01 28 29 30 50 52 Gas pipe gaskets 110879 01 26 29 Gas adaptor 111422 01 27 28 29 30 49 50 51 52 53 Venturi 110881 01 50 23 52 53 51 24A 24B 24C 25...

Страница 91: ...Key No Description Part Number 120 150 180 31A 31B 31C 31D 31E 31F 31G 31H Condensate Trap 110589 01 32 Front Door 110596 01 33 Vent connector 107160 01 42 Side panel 110725 01 111565 01 45 46 Wall b...

Страница 92: ...al number 37 Model Key 38 120 VAC Connection Board 110726 01 43 Low Voltage Connection Board 110594 01 48 Fuse 0 5A 5 x 20 mm 250V Slow Blow 111420 01 Fuse 1 0A 5 x 20 mm 250V Slow Blow Fuse 5 0A 5 x...

Страница 93: ...Auto Reset LWCO 105591 01 Manual Reset LWCO 108182 01 Fernox Alphi 11 108862 01 Hydronic System Corrosion and Lime scale Inhibitor 108863 01 Header Sensor 108703 01 Outdoor Temperature Sensor 108681...

Страница 94: ...peration of cooling system Figure A 1 Isolated Boiler from Refrigeration System Water Chiller Shut off Valves Expansion Tank Circulator Return main from combined heating cooling system Supply main to...

Страница 95: ...n if it is not safety relief valvemayopenfrequently resultinginregular additions of make up water D If an automatic fill valve is installed installation of a water meter in fill line is strongly recom...

Страница 96: ...t is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirement...

Страница 97: ...ll horizontally vented gas fueled equipment does not provide the parts for venting the flue gases but identifies special venting systems the following requirements shall be satisfied by the manufactur...

Страница 98: ...dant 5 min ensuite d terminer si le coupe tirage d borde l ouverture de d charge Utiliser la flamme d une allumette ou d une chandelle ou la fum e d une cigarette d un cigare ou d une pipe 6 Une fois...

Страница 99: ...99 110332 02 6 22 PHTM II Installation Operating Service Instructions SERVICE RECORD SERVICE PERFORMED DATE...

Страница 100: ...100 110332 02 6 22 PHTM II Installation Operating Service Instructions Velocity Boiler Works LLC P O Box 14818 3633 I Street Philadelphia PA 19134 www velocityboilerworks com...

Отзывы: