www.velocitydetection.com                        Doc:   GLT-294-7-5                      Issue: 001                              Date: 05/03/2020

 

 

Specifications 

Specification 

VL-NWM 

Part Number 

62-430 

Design Standard 

UL864 10

th

 Edition 

Approval 

UL Laboratories 

Communication Protocol 

RS485 

Maximum Network Size 

64 Nodes 

Maximum Distance Between 
Nodes 

1KM 

(using a screened data cable) 

100M 

(using a standard fireproof cable)

 

Maximum Ground Fault 
Impedance

 

10KΩ

 

Network Wiring Typologies 

Bus  
Ring 

(recommended)

 

Operating Temperature 

0°C (32°F) to 49°C (120°F) 

Max Humidity 

93% Non-Condensing 

Size (mm) (HxWxD) 

105mm x 57mm x 47mm 

Weight 

0.15KG 

Recommended Cable 

Belden Screened Data Cable 

 