Emergency Exit
An emergency exit is reserved for emergency cases only. The egress button can be programmed to offer an exit delay
with warning beeps and even to activate an alarm output to trigger an alarm system when the door is forced open or
remains open after the exit delay expired. This is a useful feature to attract the attention of the person on duty.
WARNING
Do not enable Egress Delay if your main concern is instantly opening the door for leaving.
Make sure the Egress Delay does not affect the safety in your service area before enabling the function in Location 90.
The default setting of the system is NO DELAY.
Egress mode, delay, warning beep and alarm (location 90)
Location
Configurations
Delay time
Validation
9 0
1 - 6
0 or 1
–
9 9 9
#
(1)
(2)
(3)
(4)
1.
Location
•
Key in location 9 0
2.
Configurations of the Egress Warning and Alarm:
•
1:
Pulse Mode, no Warning beeps, no Alarm
(default). In this mode, User Group 1 is activated after a short
press on the Egress button. No warning or alarm is given during the Egress Delay. Well suited for a silent area.
The people have to wait until the Egress Delay has expired for the door to open.
•
2:
Pulse Mode with Warning Beeps, no Alarm
. In this mode, User Group 1 is activated after a short press on the
Egress button. The keypad emits Warning beeps during the Egress Delay. Well suited for a place where
attention is required. The keypad beeps during the delay, while people are waiting for the door to open.
•
3:
Pulse Mode with Warning Beeps & Alarm
. In this mode, User Group 1 is activated after a short press on the
Egress button. The keypad emits Warning Beeps and activates its Alarm Output
13
during the Egress Delay. Well
suited for a door for authorized people only. This is usually an Emergency Exit. The door can be opened using
the keypad/card reader without triggering the Warning and Alarm Output.
•
4:
Holding Mode, no Warning beeps, no Alarm
. In this mode, User Group 1 is activated after pressing and
holding the Button until the Egress Delay expires. No warning or alarm is given during the Egress Delay. Well
suited for a silent area. In Holding mode it is required to press & hold the button until the Egress Delay expires
for the door to open.
•
5:
Holding Mode with Warning Beeps, no Alarm
. In this mode, User Group 1 is activated after pressing and
holding the Button until the Egress Delay expires. The keypad emits Warning Beeps during the Egress Delay.
Well suited for a place where attention is required. The keypad beeps while the button is kept pressed and the
people are waiting for the door to open.
•
6:
Holding Mode with Warning Beeps & Alarm
. In this mode, User Group 1 is activated after pressing and
holding the Button until the Egress Delay expires. The keypad emits Warning Beeps and activates its Alarm
Output
during the Egress Delay. This is usually an Emergency Exit. The door can be opened using the
keypad/card reader without triggering the Warning and Alarm Output.
3.
Egress Delay Timer
•
0:
No Delay
(default). User Group 1 channel activates instantly when the Egress Button is pressed.
13
See “