REMARKS
1. ADRESSING IN A VELBUS INSTALLATION
We recommend addressing the VMB1BLS in advance. To do so, connect the VMB1BLS to a Velbus (test)
installation and use the function “Address management” with automatic detection in Velbuslink*
(for full instructions, see the VMB1BLS extended user manual on www.velbus.eu > Downloads). Velbuslink will
automatically detect the VMB1BLS when the “up” or “down” push buttons are operated (connect
④
or
⑥
to
⑤
).
In case the VMB1BLS was not addressed in advance, this can be done afterwards as follows:
• in Velbuslink, right click on a shutter channel of a VMB1BLS that needs to be addressed and select “Operate”
• check which of the installed shutters goes up or down
• you now know which VMB1BLS module in Velbuslink corresponds to this shutter.
2. STANDALONE USE
The VMB1BLS can also be used as a standalone shutter controller (without Velbus installation). In this case, the
VMB1BLS needs only to be powered with 12..18 V DC/100 mA (connections
⑦
and
⑧
) without connecting the BUS
H
⑨
or BUS L
⑩
. The shutter can directly be operated through the push button(s) connected to “button up”
④
,
“button common”
⑤
and “button down”
⑥
.
3. TERMINATOR
Every Velbus module has a terminator switch or jumper
⑪
. In a typical Velbus installation
all terminators have to
be open except two
. These two closed terminators are ideally positioned as far as possible from each other.
In a standalone installation of the VMB1BLS, the state of the terminator is of no importance.
a
*Version 9.28 or higher
Содержание VMB1BLS
Страница 3: ...www velbus eu 3 b a c...
Страница 4: ...4 www velbus eu 1 VELBUS 24 V DC MOTOR 230 V AC MOTOR b a c...
Страница 5: ...www velbus eu 5 2 STANDALONE 24 V DC MOTOR 230 V AC MOTOR b a c 1 PUSH BUTTON...
Страница 12: ...Velbus Legen Heirweg 33 Gavere Belgium Velbus www velbus eu Velbus Visit us at www VELBUS eu...