background image

IG-305-EN version 01; 07/04/2020

18

Recommended sequence of operations

General Instructions

Outdoor cubicles: 

cgmcosmos

cgm

.3 and 

cgm

.800 systems

3. 

From inside the cable compartment, unscrew the 

12 DIN933M8 hex bolts (6 on each side) that secure the 

cubicles to the external enclosure. 

Tool:

 13 open-end wrench.

If a relief duct is fi tted, also unscrew the 12 M8 bolts 

(DIN 933) for anchoring the assembly to the relief duct, 

located at the bottom rear.

Figure 5.5. 

Anchoring bolt position relief duct with 

enclosure

Figure 5.6. 

Bolt position inside the cable compartment

4. 

Remove the external enclosure, lifting it around 100 

mm, and withdraw toward the rear section using slings 

or chains secured to the side lifting brackets at the top 

of the enclosure. The angle of pull must be as vertical 

as possible (with an angle greater than 60º from the 

horizontal). 

Maximum weight of the enclosure: 300 kg.

Figure 5.7. 

Removing the external enclosure

Содержание Ormazabal gmcosmos

Страница 1: ...LIB Outdoor cubicles cgmcosmos cgm 3 and cgm 800 systems General Instructions IG 305 EN version 01 07 04 2020...

Страница 2: ...ectrical installations Personnel must be fully familiar with the instructions and warnings contained in this manual and in other recommendations of a more general nature which are applicable to the si...

Страница 3: ...Sea transport 10 3 Storage 11 4 Installation 12 4 1 Unpacking the equipment 12 4 2 Fastening outdoor cubicles to the floor 12 4 3 Earthing the equipment 14 5 Recommended sequence of operations 15 5 1...

Страница 4: ...tructions of the switchgear system of the cubicles namely the IG 078 in the case of cgm IG 136 in the case of cgm 3 or IG 284 in the case of cgm 800 1 1 Models Multifunctional switchgear Functions 2lv...

Страница 5: ...cription 1 2 Main components 1 cgmcosmos cgm 3 or cgm 800 cubicles 2 Cable compartment cover 3 External enclosure 3 1 Doors 3 2 External enclosure bottom cover Figure 1 1 Main components outdoor cubic...

Страница 6: ...C AF 25 kA 1 s IAC AFL 25 kA 1 s IAC AFLR 25 kA 1 s IP rating external enclosure IP 54 Standard unit colour RAL grey 7035 Gas output to trench as standard Optional gas output upwards via the relief du...

Страница 7: ...LV 2158 1026 1889 1102 lv LV 1142 1026 1889 601 l2v LVV 1742 1026 1889 905 Upwards gases 2lv LVL 1560 1070 2074 898 3lv LVLL 1978 1070 2074 1118 2l2v LVLV 2160 1070 2074 1234 lv LV 1142 1070 2074 704...

Страница 8: ...height 2000 m Solar radiation 1000 W m2 Ambient air pollution dust smoke corrosive and or flammable gases vapours or salt Medium Wind speed 34 m s Vibrations due to causes external to the switchgear...

Страница 9: ...ment The switchgear must always be kept upright directly on the ground or on a pallet depending on the type of handling involved Outdoor units must be handled using lifting systems with slings or chai...

Страница 10: ...s commissioned 2 2 2 Sea transport Outdoor cubicles can be transported completely assembled in an ISO container The containers recommended for sea transport are standard dry van or high cube In order...

Страница 11: ...ort and in storage must not exceed 2000 m 5 The ambient air must not have any significant contamination from dust smoke corrosive and or inflammable gases vapours or salt 6 The switchgear must be prot...

Страница 12: ...2 Completely remove the cellophane 3 Detach the white polystyrene corner pieces 4 Unscrew the fixings between the base and the pallet 5 Remove the pallet handling the cubicle as indicated in section...

Страница 13: ...nt for anchoring Cubicle Module Configuration b f cgm 3 cgm 800 2lv LVL 1386 540 3lv LVLL 1804 540 2l2v LVLV 1986 540 lv LV 968 540 l2v LVV 1568 540 cgmcosmos 2lv LVL 1031 540 3lv LVLL 1378 540 2l2v L...

Страница 14: ...ram outdoor cgmcosmos 2lv with upwards gas output Figure 4 7 Anchoring diagram outdoor cgmcosmos 3lv with upwards gas output Figure 4 8 Anchoring diagram outdoor cgmcosmos 2l2v with upwards gas output...

Страница 15: ...s Recommended sequence of operations 5 Recommended sequence of operations 5 1 Access to the driving mechanism and cable compartment Proceed as follows to access the cubicle cable compartment and drivi...

Страница 16: ...ubicles cgmcosmos cgm 3 and cgm 800 systems 2 Release the two bolts at the top and bottom of the right hand door Figure 5 2 Interior bolt position in the right hand door 3 Remove the 4 vandal proof sc...

Страница 17: ...owed for dismantling and removing the external enclosure 1 Follow steps 1 to 3 in the above sequence for access to the driving mechanisms and cable compartment 2 Remove the two cable compartment cover...

Страница 18: ...DIN 933 for anchoring the assembly to the relief duct located at the bottom rear Figure 5 5 Anchoring bolt position relief duct with enclosure Figure 5 6 Bolt position inside the cable compartment 4 R...

Страница 19: ...as indicated in this Standard durability is not a warranty period but rather a technical consideration that helps establish a maintenance period For other categories of corrosiveness and or durabilit...

Страница 20: ...ation Avoid rubbing solid sediments on painted surfaces to prevent scratching For this purpose it may be necessary to remove larger solid particles by hand and the rest with a soft brush and or a vacu...

Страница 21: ...llows Any scratches or deterioration during assembly handling or installation are not acceptable If scratches are detected upon delivery of the equipment this must be reported to Ormazabal s technical...

Страница 22: ...reas Figure 6 1 Example of hand brush 6 A rotary tool with a soft brush can be used if the oxidation is persistent and cannot be removed with manual brushing Figure 6 2 Example of rotary tool with bru...

Страница 23: ...d for on site recovery since the application of powder based paints is not feasible Primer Epoxy based liquid primer with high zinc content Paint RAL 7035 matt polyurethane bi component liquid paint A...

Страница 24: ...installed for various reasons If any of the stated auxiliary components need to be changed the corresponding spare parts kit must be ordered and the instructions given in the corresponding documentat...

Страница 25: ...Notes IG 305 EN version 01 07 04 2020 25 General Instructions Outdoor cubicles cgmcosmos cgm 3 and cgm 800 systems Notes...

Страница 26: ...Notes IG 305 EN version 01 07 04 2020 26 Notes General Instructions Outdoor cubicles cgmcosmos cgm 3 and cgm 800 systems...

Страница 27: ......

Страница 28: ...Subject to change without prior notice For further information please ask Ormazabal Ormazabal y C a IGORRE Spain www ormazabal com...

Отзывы: