Veichi Electric VC-4AD Скачать руководство пользователя страница 7

5    Installation 

5.1    Size specification 

9 1 . 7

3 2

90

99.2

4 0

R U N

E R R

V C - 4 A D

V E I C H I

24+

V1+

I1+

V2+

I2+

V3+

I3+

V4+

I4+

VI4-

VI3-

VI2-

VI1-

PG

COM

 

Figure 5-1 External dimensions and mounting hole dimensions (unit: mm) 

5.2    Installation method 

              The installation method is the same as that for the main module, please refer to the VC Series Programmable Controllers 

User Manual for details. An illustration of the installation is shown in Figure 5-2 

.

 

 

35mm wide DIN slot

Press back the DIN slot snap

IN

0UT

PWR RUN ERR

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

00

01

02

03

04

05

06

07

10

11

12

13

14

15

VC1-1614MAR

VEICHI

RU N

ER R

VC-4AD

VEICHI

24

+

V1

+
I1

+

PG

COM

VI
1-

V2

+
I2

+

VI

2

-

V3

+
I

3+ VI

3-

V

4+
I4

+

VI
4-

 

Figure 5-2 Fixing with DIN slot 

6    Operational checks 

6.1    Routine checks 

1. Check that the analogue input wiring meets the requirements (see 1.5 Wiring instructions). 

2. Check that the VC-4AD expansion connector is reliably plugged into the expansion connector. 

3. Check that the 5V and 24V power supplies are not overloaded. Note: The power supply for the digital part of the VC-4AD 

comes from the main module and is supplied via the expansion interface. 

4. Check the application to ensure that the correct operating method and parameter range has been selected for the application. 

5. Set the VC main module to RUN. 

6.2    Fault checking 

If the VC-4AD is not running properly, check the following items. 

●Checking the status of the main module "ERR" indicator. 

blinking: check whether the expansion module is connected and whether the configuration model of the special module is the 

same as the actual connected module model. 

extinguished: the extension interface is correctly connected. 

●Check the analogue wiring. 

Confirm that the wiring is accurate and can be wired as shown in Figure 1-5.●Check the status of the module's "ERR" indicator 

Lit: 24Vdc power supply may be faulty; if 24Vdc power supply is normal, the VC-4AD is faulty. 

Содержание VC-4AD

Страница 1: ...vant industry strictly observe the relevant equipment precautions and special safety instructions provided in this manual and perform all operations of the equipment in accordance with the correct ope...

Страница 2: ...tage signal input 16 Reserved 17 I4 Channel 4 current signal input 18 VI4 Channel 4 common ground end 1 3 Terminal definition table Note For each channel voltage and current signals cannot be input at...

Страница 3: ...input and the current input for that channel 4 If there is excessive electrical interference connect the shielding ground FG to the module earth terminal PG 5 Ground the module s earth terminal PG wel...

Страница 4: ...e the linear relationship between the channel analogue input quantity A and the channel digital output quantity D which can be set by the user Each channel can be understood as the model shown in Figu...

Страница 5: ...g to digital 10000 Input 0V corresponding to digital quantity 0 Input 10V corresponding to digital quantity 10000 Figure 3 3 Example of a feature change 4 Programming examples 4 1 Programming example...

Страница 6: ...annel one setup 3 Click on to configure the second channel mode 4 3 Basic Application Channel 2 Setup 4 Click on to configure the third channel mode and click on Confirm when finished 4 4 Basic applic...

Страница 7: ...ing instructions 2 Check that the VC 4AD expansion connector is reliably plugged into the expansion connector 3 Check that the 5V and 24V power supplies are not overloaded Note The power supply for th...

Страница 8: ...function other than its normal function 5 The service charge will be calculated on the basis of the actual cost and if there is another contract the contract will take precedence 6 Please make sure th...