background image

 

 

32

speedover-cur

rent 

  Power grid voltage is too low. 

it. 

  Check input power,clear fault. 

 

E.oL1 

Motor 

over-load 

  V/F curve setting is not 

suitable. Or torque boost too high. 

  Power grid voltage is too low. 

  incorrect overload protection 

setting. 

  Locked-rotor run or too heavy 

load. 

  Universal motor long time low 

speed run. 

  Reset V/F curve or torque 

boost value. 

  Check input power,clear fault. 

  Unreasonable F5.06 setting. 

  Adjust load or select inverter 

with right capacitance.   

  If need long time low speed 

run,please choose special motor 

for inverter. 

 

E.oL2 

Inverter 

over-load 

  Load is too heavy. 

  Acceleration time is too short. 

  Start running motor. 

  V/F curve setting is not 

suitable.Or torque boost too high. 

  Select inverter with right 

capacitance. 

  Prolong acceleration time 

  Restart motor until it totally 

stop.Set F1.00 as 1or2. 

 

  Reset V/F curve or torque 

boost value. 

 

E. SC 

System 

abnormality 

  Acceleration time is too short. 

  Short circuit between inverter 

output phases or earth. 

  Module is damaged. 

  Electromagnetic disturb. 

  Prolong acceleration time. 

  Check periphery equipments 

and restart afrer fault cleared.         

  Seek support from factory. 

  Check system wiring, earth, 

shield and deal as required.   

 

E.oH 

Inverter 

over-heat 

  Temperature is too high. 

  Air channel is blocked. 

  Fan connection    parts is 

loose. 

  Fan is damaged. 

  Temperature detection circuit 

fault 

  Make the environment 

meeting the requirement. 

  Clear the air channel. 

  Check and re-connect the 

wire 

  Change the same new fan.   

  Seek support from factory. 

 

E.TE1 

Motor static 

detection fault   

  Detection overtime 

  Perform static detection while 

motor is running. 

  Capacitance difference is too 

big between motor and inverter. 

  Motor parameter setting 

mistake. 

  Check motor connection 

wire. 

  Detect after motor stop totally. 

  Change inverter model. 

  Reset parameter according 

to nameplate. 

 

E.TE2 

Moror rotation 

detection fault 

  Detect while motor is running. 

  Detect with load. 

  Detection overtime 

  Capacitance difference is too 

big between motor and inverter. 

  Motor parameter setting 

mistake. 

  Detect after motor stop totally. 

  Re-detect without load. 

  Check motor connection 

wire. 

  Change inverter model. 

  Reset parameter according 

to nameplate. 

Содержание AC70E-S2-R40G

Страница 1: ...messages of installing wiring keyboard operation simple function table troubleshooting maintenance only For parameters setting detail pls read AC70 general used series manual or consult us For the bes...

Страница 2: ...anger If not abide the regulations or requirements in this manual there is danger of body injuryeven death and machinesystemdamage Do not wire while the power is conneted Otherwise there is danger of...

Страница 3: ...e is ok pls open it and check the inverter If damage caused in transport it is not duty of Veich company But please contact Veich or the transport company immediately After checking the product please...

Страница 4: ...age compensation function if motor rated voltage is 100 the voltage can be set in the 50 100 scope the voltage output should not exceed the input voltage AVR adjust When the grid voltage fluctuates ch...

Страница 5: ...and avoid the impact of electromagnetic interference Ensure all equipments connected to frequency inverter are connected to star earth or common earth bus by short and thick cable as well as frequenc...

Страница 6: ...c condition of safe and reliable running of the product For right earthing please read the following notice carefully In order to avoid electric shock earthing cable should be the size as electric equ...

Страница 7: ...e without metal dust oil water or etc into inverter please do not install inverter on flammable material such as food and etc Place without radioactive material or flammablematerial Place without pois...

Страница 8: ...inverter cooling please follow installation conditions as below It should adopts hanging style or closet style with upright installation and keeps enough space with surroundings or the wall Multi inve...

Страница 9: ...inverter and keyboard W1 H 1 W H D D1 MODEL WW W1 H H1 D D1 INSTALLATION APERTURE AC70E S2 R40G 88 75 142 5 129 5 142 132 5 AC70E S2 R75G AC70E S2 1R5G AC70E T3 R75G AC70E T3 1R5G AC70E S2 2R2G 106 90...

Страница 10: ...to obey aimed to ensuring safe use best performance and reliable running Note Analog monitor output is special output of meters such as frequcy meter current meter voltage meter and etc It can not be...

Страница 11: ...0 75 kW 200 120W 100 1 5 kW 400 300W 100 1 5 kW 100 300W 100 2 2 kW 250 400W 100 2 2 kW 75 300W 100 3 7 kW 150 500W 100 Main circuit terminals Terminal Name Function definition Braking resistance ter...

Страница 12: ...amme set definition Pls refer F 01 F 04 X2 Multi function contact input X2 X3 Multi function contact input X3 X4 Multi function contact input X4 AO Analog output Physical type of output signal 0 10V 0...

Страница 13: ...oring state While given frequency or PID or given torque are set by keyboard Shift key Select digit of function no modified by up down key Select parameter digits modified by up dowm key Change LED mo...

Страница 14: ...ator and the A indicator light at the same time display value is the motor speed Flashing When the A indicator and the V indicator flashing at the same time display value is gived PID value On When th...

Страница 15: ...tting range and definition Factary default pr op ert y Refer to page Comm unicati on code E 00 Control method selection 0 Open loop vector controlwithout PG 1 V F control mode 1 69 100H E 01 Running c...

Страница 16: ...Both channel is valid if non zero value main channelpriority 3 Main channel K auxiliary channel 4 main channel K auxiliary channel 5 MAX main channel K auxiliary channel 6 MIN main channel K auxiliar...

Страница 17: ...elerate decelerate time datum point 0 Motor rated frequency 1 Maximum frequency LED hundreds digit Equidistance stop function 0 Disable 1 Enable LEDThousands digit reserve 0000 74 10FH E 16 Frequencyg...

Страница 18: ...shock is enabled 1010 77 115H E 22 V F slip compensation 0 200 100 78 116H E 23 Energy saving mode selection LED unitdigit Auto energy saving selection 0 disable 1 enable LED tens digit V F slip compe...

Страница 19: ...ng starting frequency when stop 0 00 60 00Hz 0 00Hz 81 125H E 38 DC braking time when start 0 0 10 0s 0 0s 81 126H E 39 Jump frequency 1 0 00 600 0Hz Fmax 0 00Hz 81 127H E 40 Jump frequency 2 0 00 600...

Страница 20: ...tage suppression threshold voltage 105 160 135 86 135H E 54 Ratio of dynamicbraking 0 100 80 86 136H E 55 DC bus under voltage protecting value 60 90 65 86 137H E 56 Reserve 86 138H E 57 Reserve 86 13...

Страница 21: ...ent in deceleration suppression 0 Disable 1 Enable 2 Enable frequency reducing for protecting over current 0001 91 143H External terminal parameters Code funcion Fucntion name Setting range and define...

Страница 22: ...2 18 Frequency main channel selection terminal3 19 Frequency main channel selection terminal4 20 Program running pause 21 Program restart 22 Timer trigger terminal 23 Timer reset terminal 24 Counter r...

Страница 23: ...ute UP DW adjusting LED hundred digit STOP RESE of keypad effective range selection 0 STOP RESE key valid only when under keypad control 1 STOP RESE key valid underany run command source LED thousand...

Страница 24: ...educing acceleration time 0 1 6500 0s 1 0s 97 217H F 24 Acceleration time 2 0 1 6500 0s 98 218H F 25 Deceleration time 2 98 219H F 26 Acceleration time 3 98 21AH F 27 Deceleration time 3 98 21BH F 28...

Страница 25: ...inal input voltage lower limit 0 00V F 42 0 50V 101 229H F 42 VS1 terminal input voltage upper limit F 41 10 00V 9 50V 101 22AH F 43 VS1 terminal input voltage gain 0 01 5 00 1 00 101 22BH F 44 VS2 te...

Страница 26: ...0 Positive characteristic 1 Negative characteristic LED ten digit AS input characteristic selection 0 Positive characteristic 1 Negative characteristic LED hundred digit VS2 input characteristic sele...

Страница 27: ...5 00 1 00 106 245H F 70 UP DW terminalpreset frequency 0 00Hz upper limit freqeuncy 0 00Hz 106 246H F 71 UP DW Power off memorized frequency 0 00Hz upper limit freqeuncy 0 00Hz 106 247H Special functi...

Страница 28: ...20 Integral time constant I 0 1 100 0s 2 0s 109 314H H 21 Differentialgain D 0 0 10 0 0 0 109 315H H 22 Sampling period 0 01 60 00s 0 10s 110 316H H 23 PID controldeviation limit 0 0 20 0 0 0 110 317...

Страница 29: ...step speed direction and accel decel time 4 113 327H H 40 6 step speed direction and accel decel time 5 113 328H H 41 7 step speed direction and accel decel time 6 113 329H H 42 8 step speed directio...

Страница 30: ...rate 0 1200bps 1 2400bps 2 4800bps 3 9600bps 4 19200bps 5 38400bps 3 116 345H H 70 Communication setting frequency ratio 0 00 20 00 1 00 116 346H H 71 Time of communication time out 0 0 6500 0s 10 0s...

Страница 31: ...tionover limit Prolong Deceleration time Reduce load inertiaor improve inverter capacitanceor add braking unit Detectpowervoltage and clear fault E oU3 Constant speedover volt age Power voltage fluctu...

Страница 32: ...isdamaged Electromagneticdisturb Prolong acceleration time Checkperipheryequipments and restart afrer fault cleared Seeksupport from factory Check system wiring earth shield and dealas required E oH...

Страница 33: ...age Check keyboard wire Seeksupport from factory E CPE Parameter copy fault Parameter copy communication is fault Copy keyboard is not match the inverter Check wire Select the specified external keybo...

Страница 34: ...n periodic Main circuit panorama If the fastener loosen whether having the hot shot trail whether having discharging or not phenomenon dust are too much if the wind way is blocked up Visual tighten cl...

Страница 35: ...volt megger measures the frequency inverter Its insulation resistance should not smaller than 4M When using the general ohmmeters to measure current the current in the input end will has imbalance ph...

Страница 36: ...being authorized by our company When quality problem appears our company only undertakes three guarantee service as the 11 1 and 11 2 responsibilities above If user needs more responsibility guarantee...

Страница 37: ...tive C07H C 8 PID feedback quantitative C08H C 9 Module temperature C09H C 10 Accumulative operation time hour C0AH C 11 Accumulative operation time after latest power on Min C0BH C 12 Output current...

Страница 38: ...input terminal on off state X1 terminal stage X3 terminal stage X4 terminal stage Output terminal connect disconnect state schematic diagram Reserve Reserve Reserve Reserve Y2 terminal stage Y1 termi...

Страница 39: ...ault Units E07H Er 08 Running direction while the latest fault 0 Forward 1 reverse E08H Er 09 Running status while the latest fault 0 close down 1 stable speed 2 acceleration 3 deceleration E09H Er 10...

Отзывы: