18
6 Setup
VEGATOR 121 •
57662-EN-210714
Note:
The switching conditions in the tables are only valid if the mode
switch on the sensor is set to "
Max.
".
Sensor
Controller
Level
Sensor
current
LED yel-
low
(output)
LED red
(fault)
Relay
Fail safe
relay (op-
tional)
approx.
8 mA
ON
ON
approx.
16 mA
OFF
ON
any
< 3.6 mA
> 21 mA
OFF
OFF
Sensor
Controller
Level
Sensor
current
LED yel-
low
(output)
LED red
(fault)
Relay
Fail safe
relay (op-
tional)
approx.
16 mA
ON
ON
approx.
8 mA
OFF
ON
any
< 3.6 mA
> 21 mA
OFF
OFF
Overfill protection, point
level
Dry run protection, point
level