VEGASON 63 • Four-wire 4 … 20 mA/HART
51864-EN-210616
7 Supplement
7.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions which are included in delivery are valid for
approved instruments (e.g. with Ex approval). These data can differ from the data listed herein, for
example regarding the process conditions or the voltage supply.
All approval documents can be downloaded from our homepage.
Input variable
Measured variable
distance between lower edge of the transducer and
medium surface
Measuring range
Ʋ
Liquids
up to 15 m (49.21 ft)
Ʋ
Bulk solids
up to 7 m (22.97 ft)
Dead zone
0.6 m (1.969 ft)
Electromechanical data - version IP66/IP67
Cable entry
Ʋ
Double chamber housing
–
1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x
blind plug M20 x 1.5; plug M12 x 1 for VEGADIS 61
(optional)
or:
–
1 x closing cap ½ NPT, 1 x blind plug ½ NPT, plug
M12 x 1 for VEGADIS 61 (optional)
or:
–
1 x plug (depending on the version), 1 x blind plug
M20 x 1.5; plug M12 x 1 for VEGADIS 61 (optional)
Spring-loaded terminals for wire cross-
section
< 2.5 mm² (AWG 14)
Voltage supply
Operating voltage
Ʋ Non-Ex and Ex-d instrument
20 … 72 V DC, 20 … 253 V AC, 50/60 Hz
Power consumption
max. 4 VA; 2.1 W