Category 1G instruments
Temperature class
Temperature on the antenna
Ambient temperature on the elec
-
tronics
T5
-20 … +42 °C
-20 … +42 °C
T4, T3, T2, T1
-20 … +60 °C
-20 … +60 °C
For applications requiring instruments of category 1G the process pressure of the media must be
between 0.8 … 1.1 bar. The application conditions when operating in the absence of explosive
mixtures can be found in the manufacturer information.
Category 1/2G instruments
Temperature class
Temperature on the antenna
Ambient temperature on the elec
-
tronics
T6
-20 … +60 °C
-40 … +46 °C
T5
-20 … +60 °C
-40 … +61 °C
T4, T3, T2, T1
-20 … +60 °C
-40 … +80 °C
For applications requiring instruments of category 1G the process pressure of the media must be
between 0.8 … 1.1 bar. If the VEGAPULS PS61(*).C****P/K/F/L**** are operated at temperatures
higher than those specified in the above table, please make sure by means of appropriate measures
that there is no danger of ignition from the hot surfaces. The max. permissible temperature on the
electronics/housing should not exceed the values according to the above table.
Please make sure that the sensor also in case of failure does not generate heat itself. Responsibility
for safe operation of the equipment, with respect to pressures/temperatures of the materials used,
rests with the operator.
The prerequisites for operation in the absence of explosive mixtures can be found in the manufac
-
turer specifications.
Category 2G instruments
Temperature class
Temperature on the antenna
Ambient temperature on the elec
-
tronics
T6
-60 … +80 °C
-40 … +46 °C
T5
-60 … +80 °C
-40 … +61 °C
T4, T3, T2, T1
-60 … +80 °C
-40 … +80 °C
If the VEGAPULS PS61(*).C****P/K/F/L**** are operated at higher temperatures than those speci
-
fied in the above table, please make sure by means of appropriate measures that there is no danger
of ignition from hot surfaces. The max. permissible temperature on the electronics/housing must not
exceed the values specified in the above table.
Please make sure that the sensor also in case of failure does not generate heat itself. Responsibility
for safe operation of the equipment, with respect to pressures/temperatures of the materials used,
rests with the operator.
The prerequisites for operation in the absence of explosive mixtures can be found in the manufac
-
turer specifications.
6
Protection against static electricity
The VEGAPULS PS61(*).C****P/K/F/L**** in versions with electrostatically chargeable plastic parts,