VEGAPULS 61

37991-EN-200303

Category 1G instruments

Temperature class

Temperature on the antenna

Ambient temperature on the elec

-

tronics

T5

-20 … +42 °C

-20 … +42 °C

T4, T3, T2, T1

-20 … +60 °C

-20 … +60 °C

For applications requiring instruments of category 1G the process pressure of the media must be 

between 0.8 … 1.1 bar. The application conditions when operating in the absence of explosive 

mixtures can be found in the manufacturer information.

Category 1/2G instruments

Temperature class

Temperature on the antenna

Ambient temperature on the elec

-

tronics

T6

-20 … +60 °C

-40 … +46 °C

T5

-20 … +60 °C

-40 … +61 °C

T4, T3, T2, T1

-20 … +60 °C

-40 … +80 °C

For applications requiring instruments of category 1G the process pressure of the media must be 

between 0.8 … 1.1 bar. If the VEGAPULS PS61(*).C****P/K/F/L**** are operated at temperatures 

higher than those specified in the above table, please make sure by means of appropriate measures 

that there is no danger of ignition from the hot surfaces. The max. permissible temperature on the 

electronics/housing should not exceed the values according to the above table.

Please make sure that the sensor also in case of failure does not generate heat itself. Responsibility 

for safe operation of the equipment, with respect to pressures/temperatures of the materials used, 

rests with the operator.

The prerequisites for operation in the absence of explosive mixtures can be found in the manufac

-

turer specifications.

Category 2G instruments

Temperature class

Temperature on the antenna

Ambient temperature on the elec

-

tronics

T6

-60 … +80 °C

-40 … +46 °C

T5

-60 … +80 °C

-40 … +61 °C

T4, T3, T2, T1

-60 … +80 °C

-40 … +80 °C

If the VEGAPULS PS61(*).C****P/K/F/L**** are operated at higher temperatures than those speci

-

fied in the above table, please make sure by means of appropriate measures that there is no danger 

of ignition from hot surfaces. The max. permissible temperature on the electronics/housing must not 

exceed the values specified in the above table.

Please make sure that the sensor also in case of failure does not generate heat itself. Responsibility 

for safe operation of the equipment, with respect to pressures/temperatures of the materials used, 

rests with the operator.

The prerequisites for operation in the absence of explosive mixtures can be found in the manufac

-

turer specifications.

Protection against static electricity

The VEGAPULS PS61(*).C****P/K/F/L**** in versions with electrostatically chargeable plastic parts, 

Содержание VEGAPULS 61 Series

Страница 1: ...8 7 Use of an overvoltage arrester 9 8 Grounding 9 9 Impact and friction sparks 9 10 Material resistance 9 11 Mounting with external display unit VEGADIS 61 81 9 12 Removing and replacing the red thre...

Страница 2: ...k ytt varten EL DE Die vorliegenden Sicherheitshinweise sind im Download unter www vega com standard m ig in den Sprachen deutsch englisch franz sisch und spanisch verf gbar Weitere EU Landessprachen...

Страница 3: ...tible liquids gases mist or vapour The VEGAPULS PS61 C P K F L are suitable for use in hazardous atmospheres of all combustible materials of explosion group IIA IIB and IIC for applications requiring...

Страница 4: ...s L Two wire Foundation Fieldbus with increased sensitivity g Housing Protection K Plastic single chamber IP66 IP67 A Aluminium single chamber IP66 IP68 0 2 bar H Special colour Aluminium single chamb...

Страница 5: ...ns then these will be mentioned explic itly with their type code 4 Technical data Electrical data Type of protection intrinsic safety Ex i Power supply and signal circuit termi nals 1 2 in electronics...

Страница 6: ...insic safety Ex ia IIC Only for connection to the display and adjust ment module PLICSCOM or VEGACONNECT PTB 07 ATEX 2013 X With the double chamber housing version the display and adjustment module ma...

Страница 7: ...or also in case of failure does not generate heat itself Responsibility for safe operation of the equipment with respect to pressures temperatures of the materials used rests with the operator The pre...

Страница 8: ...trostatically connected to the local potential equalisation transfer resistance 1 M e g via the ground terminal when used as category 1G or 1 2G instru ments Metallic adapter flanges must be earthed e...

Страница 9: ...ice and the openings must be sealed according to the requirements of the type of protection and the IP protection type specified on the type label When using certified i e suitable cable glands sealin...

Страница 10: ...11 Notes VEGAPULS 61 37991 EN 200303...

Отзывы: