11 Diagnostics and servicing
VEGAPULS 21 • Two-wire 4 … 20 mA/HART
58351-EN-191014
Code
Text message
Cause
Rectification
DevSpec
State in CMD 48
F080
General software
error
General software error
Disconnect operating voltage
briefly
Bit 5 of Byte 0 … 5
F105
Determine meas-
ured value
The instrument is still in the start
phase, the measured value could
not yet be determined
Wait for the end of the switch-on
phase
Duration up to approx. 3 minutes
depending on the version and pa-
rameter settings
Bit 6 of Byte 0 … 5
F113
Communication
error
EMC interference
Remove EMC influences
Bit 12 of Byte 0 … 5
F125
Impermissible elec-
tronics temperature
Temperature of the electronics in
the non-specified range
Check ambient temperature
Insulate electronics
Use instrument with higher tem-
perature range
Bit 7 of Byte 0 … 5
F260
Error in the cali-
bration
Error in the calibration carried out
in the factory
Error in the EEPROM
Exchanging the electronics
Send instrument for repair
Bit 8 of Byte 0 … 5
F261
Error in the instru-
ment settings
Error during setup
False signal suppression faulty
Error when carrying out a reset
Repeat setup
Carry out a reset
Bit 9 of Byte 0 … 5
F264
Installation/Setup
error
Adjustment not within the vessel
height/measuring range
Max. measuring range of the in-
strument not sufficient
Check or correct installation and/
or parameter settings
Use an instrument with bigger
measuring range
Bit 10 of Byte 0 … 5
F265
Measurement func-
tion disturbed
Sensor no longer carries out a
measurement
Operating voltage too low
Check operating voltage
Carry out a reset
Disconnect operating voltage
briefly
Bit 11 of Byte 0 … 5
Code
Text message
Cause
Rectification
DevSpec
State in CMD 48
C700
Simulation active
A simulation is active
Finish simulation
Wait for the automatic end after
60 mins.
"Simulation Active"
in "Standardized
Status 0"
Code
Text message
Cause
Rectification
DevSpec
State in CMD 48
S600
Impermissible elec-
tronics temperature
Temperature of the electronics in
the non-specified range
Check ambient temperature
Insulate electronics
Byte 23, Bit 4 of
Byte 14 … 24
Function check
Out of specification