E
rror
C
ause
R
emoval
W
hen an additio
-
nal instrument is
connected
,
the
H
1
segment fails
.
M
ax
.
supply cur
-
rent of the seg
-
ment coupler
exceeded
M
easure the current consumption
,
reduce size of segment
M
easured value
on the indicating
and adjustment
module does not
correspond to the
value in the
PLC
T
he menu item
"
D
isplay
-
D
is
-
play value
"
is
not set to
"
AI
-
O
ut
"
C
heck values and correct
,
if neces
-
sary
I
nstrument does
not appear during
connection setup
P
ro
fi
bus
DP
cab
-
le pole
-
reversed
C
heck cable and correct
,
if necessary
I
ncorrect termina
-
tion
C
heck termination at the beginning
and end points of the bus and termin
-
ate
,
if necessary
,
according to the
speci
fi
cation
I
nstrument not
connected to the
segment
C
heck and correct
,
if necessary
I
n
E
x applications
,
the regulations for the wiring of intrinsically safe
circuits must be observed
.
?
E
013
l
no measured value available
7
)
à
E
xchange the instrument or send it in for repair
?
E
017
l
A
djustment span too small
à
repeat with modi
fi
ed values
?
E
036
l
no operable sensor software
à
C
arry out a software update or send instrument for repair
?
E
041
l
H
ardware error
à
E
xchange the instrument or send it in for repair
7
)
F
ault message can also appear if the pressure is higher than the nominal
range
.
E
rror messages via the
indicating and adjust
-
ment module
VEGADIF
65
•
F
oundation
F
ieldbus
73
9
M
aintenance and fault recti
fi
cation
36130
-
EN
-
110510
Содержание VEGADIF 65
Страница 1: ...Operating Instructions VEGADIF 65 Foundation Fieldbus Document ID 36130 Di erential pressure...
Страница 4: ...Information Editing status 2011 05 09 4 VEGADIF 65 Foundation Fieldbus Contents 36130 EN 110510...
Страница 102: ...102 VEGADIF 65 Foundation Fieldbus Index 36130 EN 110510...
Страница 103: ...VEGADIF 65 Foundation Fieldbus 103 Index 36130 EN 110510...