13 Supplement
VEGABAR 39 • Three-wire 1 x transistor or 4 … 20 mA
57536-EN-200831
1
2
0 °C
(32 °F)
40 °C
(104 °F)
70 °C
(158 °F)
100 °C
(212 °F)
90 °C
(194 °F)
Fig. 34: Temperature derating VEGABAR 39, with activated Bluetooth communication
1 Process temperature
2 Ambient temperature
SIP process temperature
13)
Device configuration suitable for vapour, i.e. measuring cell seal EPDM or FFKM (Perlast G74S),
previous CIP cleaning up to max. +80 °C (+176 °F):
14)
Vapour stratification up to
Ʋ 15 min
+150 °C (+302 °F)
Ʋ 30 min
+140 °C (+284 °F)
Ʋ 1 h
+135 °C (+275 °F)
Process pressure
Max. permissible process pressure
see specification "
MWP
" on the type label
15)
Min. permissible process pressure
16)
Ʋ -40 … +60 °C (-40 … +140 °F)
2 mbar
abs
(200 Pa
abs
)
Ʋ +60 … +130 °C (-40 … +266 °F)
50 mbar
abs
(5 kPa
abs
)
Indication
Measured value and menu display
Ʋ Graphic-capable LC display, with
lighting
digital and quasianalogue indication
Ʋ Max. indicating range
-99999 … 99999
Status indication
LED illuminated ring (green-yellow-red)
Adjustment
Adjustment elements
3 x keys for menu adjustment
PC/Notebook
PACTware/DTM
Smartphone/Tablet
Adjustment app
Measuring cell temperature
Range
-40 … +130 °C (-40 … +266 °F)
Resolution
< 0.2 K
13)
SIP = Sterilization in place
14)
CIP = Cleaning in place
15)
MWP: Maximum Working Pressure
16)
Measuring ranges up to 100bar/10 MPa