TLS-IB Site Prep Manual
Mounting the TLS-IB
14
Mounting the TLS-IB
Install the TLS-IB fastening devices to the mounting surface using the hole pattern 170 x 145mm (6.7 x 5.7 inches)
shown in Figure 12. Mounting screws up to 4.7mm (3/16-inch) diameter may be used.
Mount the TLS-IB to the mounting surface using the four mounting flanges on the back of the unit. Install ducting or
conduit between the TLS-IB and the power panel. Figure 12 shows the three designated knockouts (one each on top, left
side, and bottom) through which power wiring can safely enter the TLS-IB.
Figure 12. TLS-IB Dimensions and Designated Conduit Knockouts
0.34'' (8,6) typ.
0.34'' (8,6) typ.
7.4" (188)
6.4''
(163)
5.7''
(145)
2" (50)
5.3'' (135)
1.24''
(31)
5.3'' (135)
0.54" inside (M12 conduit),
1/2'' I.P.S. (International Pipe Size) outside (PG7 conduit)
knockouts 4 places - bottom (2), left side (1), and top (1)
1/2", 3/4'', & 1'' I.P.S.
conduit knockout pattern (2 places)
Cover (shown open
for reference)
tlsnt\ibdim.eps
0.22'' (5,6) dia.
mounting holes (4 places)
0.93'' (23)
0.93'' (23)
3''
(73)
0.7''
(17)
0.93''
(23)
6.7" (170)
NOTE: Numbers
in parenthesis are
in millimetres.
0.93''
(23)